MeasType
: Selection of discrete Fourier filtered (
DFT
) or true RMS filtered (
RMS
)
signals.
RMS
is used when the harmonic contents are to be considered, for example in
applications with shunt capacitors.
Operation
: The protection can be set to
On
or
Off
.
AngleRCA
: Protection characteristic angle set in degrees. If the angle of the fault loop
current has the angle RCA, the direction to the fault is forward.
AngleROA
: Angle value, given in degrees, to define the angle sector of the directional
function, shown in Figure
.
StartPhSel
: Number of phases, with high current, required for operation. The setting
possibilities are:
1 out of 3
,
2 out of 3
and
3 out of 3
. The default setting is
1 out of 3
.
IMinOpPhSel
: Minimum current setting level for releasing the directional start signals
in % of
IB
. This setting should be less than the lowest step setting. The default setting
is 7% of
IB
.
2ndHarmStab
: Operate level of 2nd harmonic current restrain set in % of the
fundamental current. The setting range is
5 - 100
% in steps of 1%. The default setting
is 20%.
Section 9
1MRK 502 071-UEN -
Current protection
326
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...