Then the reach in primary ohms shall be set to 100% of transformer impedance. Thus
the reach shall be set to 0,26Ω primary.
Set the first zone of Full-scheme distance measuring, Mho characteristic ZMHPDIS
to disable phase-to-earth loops and enable phase-to-phase loops:
•
The parameter
GlobalBaseSel
shall be set in order to select the global base value
group GBASVAL where the base voltage
UBase
and the base current
IBase
are
defined;
UBase
is the generator rated phase-phase voltage (
UBase
=13,2kV) and
IBase
is the generator rated phase current (
IBase
=3062A).
•
Parameter
DirMode
shall be set to
Offset.
•
Parameter
OffsetMhoDir
shall be set to
Non-directional.
•
The phase-to-earth measuring loops shall be disabled by setting
OpModePE
=
Off.
•
The phase-to-phase measuring loops shall be enabled and corresponding settings
in primary ohms for forward and reserve reach and time delay shall be entered
accordingly:
•
Parameter
ZPP
shall be set to
0,260Ω.
•
Parameter
ZrevPP
shall be set to
0,260Ω.
•
Parameter
tPP
shall be set to
1,0000s.
•
Parameter
ZAngPP
shall be set to default value
85 Deg
.
Set the following for the directional element ZDMRDIR:
•
The parameter
GlobalBaseSel
shall be set in order to select the global base value
group GBASVAL where the base voltage
UBase
and the base current
IBase
are
defined;
UBase
is the generator rated phase-phase voltage (
UBase
=13,2kV) and
IBase
is the generator rated phase current (
IBase
=3062A).
•
Parameter
DirEvalType
shall be set to
Imp/Comp
.
•
Other settings can be left on the default values.
By doing this offset mho characteristic for zone one will be achieved as shown in
figure
. Note that for this particular example
ZPP
=
ZRevPP
=
0,26Ω
. Thus the
operating characteristic for this particular application will be a circle with a centre in
the impedance plane origo.
By following the same procedure other mho zones can be set.
Section 8
1MRK 502 071-UEN -
Impedance protection
186
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...