1. The recommended connection require four analog channels of the IED: two IED
voltage channels are used for the measured quantities for ROTIPHIZ; two more
IED voltage channels are used for the measured quantities for STTIPHIZ.
REX060
X61
9
8
8
9
11
10
11
10
X81
STATOR MODULE SIM
ROTOR MODULE RIM
IED
VOLTAGE MEASURE (U)
VOLTAGE MEASURE (U)
CURRENT MEASURE (U)
CURRENT MEASURE (U)
IEC11000209-1-en.vsd
IEC11000209 V1 EN
Figure 156:
Separate analog inputs for stator STTIPHIZ and rotor ROTIPHIZ
protection
2. It is possible to use a mixed connection that requires only two IED voltage
channels for both ROTIPHIZ and STTIPHIZ. REX060 outputs are connected in
series. This connection is not recommended and can be used only in applications
where it is prove the possibility to use it. the use of this connection leads to
reduced performances of both ROTIPHIZ and STTIPHIZ.
Section 8
1MRK 502 071-UEN -
Impedance protection
296
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual