Figure 208:
Alternative connections of an Overexcitation protection
OEXPVPH(Volt/Hertz)
10.4.3
Setting guidelines
10.4.3.1
Recommendations for input and output signals
Recommendations for Input signals
Please see the default factory configuration.
BLOCK
: The input will block the operation of the Overexcitation protection
OEXPVPH, for example, the block input can be used to block the operation for a
limited time during special service conditions.
RESET
: OEXPVPH has a thermal memory, which can take a long time to reset.
Activation of the RESET input will reset the function instantaneously.
Recommendations for Output signals
Please see the default factory configuration for examples of configuration.
ERROR
: The output indicates a measuring error. The reason, for example, can be
configuration problems where analogue signals are missing.
START
: The START output indicates that the level V/Hz>> has been reached. It can
be used to initiate time measurement.
TRIP
: The TRIP output is activated after the operate time for the U/f level has expired.
TRIP signal is used to trip the circuit breaker(s).
1MRK 502 071-UEN -
Section 10
Voltage protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
421
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...