used on heavy loaded, medium long lines. For short lines, the major concern is to get
sufficient fault resistance coverage. Load encroachment is not a major problem. See
section
"Zone reach setting lower than minimum load impedance"
.
R
Z1
ArgLd
RLdFw
IEC09000248-3-en.vsdx
X
RLdRv
[1]
IEC09000248 V3 EN
Figure 83:
Load encroachment phenomena and shaped load encroachment
characteristic
[1]
8.2.2.4
Short line application
In short line applications, the major concern is to get sufficient fault resistance
coverage. Load encroachment is not such a common problem. The line length that can
be recognized as a short line is not a fixed length; it depends on system parameters
such as voltage and source impedance, see table
.
Table 25:
Definition of short and very short line
Line category
Un
Un
110 kV
500 kV
Very short line
1.1-5.5 km
5-25 km
Short line
5.5-11 km
25-50 km
The IED's ability to set resistive and reactive reach independent for positive and zero
sequence fault loops and individual fault resistance settings for phase-to-phase and
phase-to-earth fault together with load encroachment algorithm improves the
possibility to detect high resistive faults without conflict with the load impedance.
For very short line applications, the underreaching zone 1 can not be used due to the
fact that the voltage drop distribution throughout the line will be too low causing risk
for overreaching.
[1] RLdRv=RLdRvFactor*RLdFw
1MRK 502 071-UEN -
Section 8
Impedance protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
193
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...