Settings on the local HMI under
Main menu/Configuration/Communication/
Ethernet configuration/Access point/AP_X
:
•
Operation: On
•
PTP: On
Two status monitoring signals can be:
•
SYNCH signal on the MUx function block indicates that protection functions are
blocked due to loss of internal time synchronization to the IED
•
MUSYNCH signal on the MUx function block monitors the synchronization flag
smpSynch
in the datastream and IED hardware time synchronization.
Using MU for time synchronization via PPS
This example is not valid when GPS time is used for differential
protection, when PTP is enabled or when the PMU report is used.
IED
MU
Analog data
PPS
IEC/UCA 61850-9-2LE
Synchronization
IEC10000061=2=en=Original.vsd
IEC10000061 V2 EN
Figure 331:
Setting example when MU is the synchronizing source
Settings on the local HMI under
Main menu/Configuration/Time/
Synchronization/TIMESYNCHGEN:1/IEC61850-9-2
:
•
HwSyncSrc
: set to
PPS
as generated by the MU (ABB MU)
•
SyncLostMode
: set to
Block
to block protection functions if time synchronization
is lost
•
SyncAccLevel
: can be set to
4μs
since this corresponds to a maximum phase angle
error of 0.072 degrees at 50Hz
Section 20
1MRK 502 071-UEN -
Station communication
694
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...