Setting
Short Description
Selected value
OilTmConstMode
Select the transformer oil time constant
mode of input to the function
Standard
OilTimeConst
Set the transformer oil time constant when
the oil time constant mode is selected as
User defined
9000.0 sec
AvgOilTmpRise
Set the transformer average oil
temperature rise for the calculation of oil
time constant
45° C
CoilCoreMass
Set the transformer coil and core assembly
mass for the calculation of oil time constant
65.0 t
OilMass
Set the transformer oil mass for the
calculation of oil time constant
35.0 t
TankMass
Set the transformer tank mass which is
having direct contact with heated oil for the
calculation of oil time constant
15.0 t
LoadLoss
Set the rated load loss of the transformer
for the calculation of oil time constant
10.0 MW
TTLoadLoss
Set the load loss of the transformer arrived
from the type test for the calculation of oil
time constant
10.0 MW
NoloadLoss
Set the rated no-load loss of the
transformer for the calculation of oil time
constant
2.0 MW
TTNoloadLoss
Set the no-load loss of the transformer
arrived from the type test for the
calculation of oil time constant
2.0 MW
WdgTmConstMode
Select the transformer winding time
constant mode of input to the function
Standard
WdgTimeConst1
Set the transformer winding time constant
for the winding 1 when the winding time
constant mode is selected as
User defined
420.0 sec
WdgTimeConst2
Set the transformer winding time constant
for the winding 2 when the winding time
constant mode is selected as
User defined
420.0 sec
WdgTimeConst3
Set the transformer winding time constant
for the winding 3 when the winding time
constant mode is selected as
User defined
420.0 sec
ConductorType
Select the transformer winding material for
the winding time constant
Calculated
Copper
WdgToOilGrad1
Set the transformer winding to oil
temperature gradient for the winding 1
when the winding time constant mode is
selected as
Calculated
20° C
WdgToOilGrad2
Set the transformer winding to oil
temperature gradient for the winding 2
when the winding time constant mode is
selected as
Calculated
20° C
WdgToOilGrad3
Set the transformer winding to oil
temperature gradient for the winding 3
when the winding time constant mode is
selected as
Calculated
20° C
Table continues on next page
1MRK 502 071-UEN -
Section 17
Monitoring
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
667
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...