15.7.3
Setting guidelines
The function does not have any parameters available in the local HMI or PCM600.
15.8
Single point generic control 8 signals SPC8GAPC
15.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single point generic control 8 signals
SPC8GAPC
-
-
15.8.2
Application
The Single point generic control 8 signals (SPC8GAPC) function block is a collection
of 8 single point commands that can be used for direct commands for example reset of
LED's or putting IED in "ChangeLock" state from remote. In this way, simple
commands can be sent directly to the IED outputs, without confirmation.
Confirmation (status) of the result of the commands is supposed to be achieved by
other means, such as binary inputs and SPGAPC function blocks.
PSTO is the universal operator place selector for all control functions.
Even if PSTO can be configured to allow LOCAL or ALL operator
positions, the only functional position usable with the SPC8GAPC
function block is REMOTE.
15.8.3
Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GAPC) function
are set via the local HMI or PCM600.
Operation
: turning the function operation
On
/
Off
.
There are two settings for every command output (totally 8):
PulseModex
: decides if the command signal for output
x
is
Latched
(steady) or
Pulsed
.
tPulsex
: if
PulseModex
is set to
Pulsed
, then
tPulsex
will set the length of the pulse (in
seconds).
Section 15
1MRK 502 071-UEN -
Control
594
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...