Generator unit transformer
IEC06000319-2-en.vsd
3I
0
IEC06000319 V2 EN
Figure 215:
Neutral point current measurement
In some power plants the connection of the neutral point resistor is made to the
generator unit transformer neutral point. This is often done if several generators are
connected to the same bus. The detection of earth-fault can be made by current
measurement as shown in figure
Generator unit transformer
IEC06000320-3-en.vsd
I
N
= I
L1
+ I
L2
+ I
L3
Other
generator
IEC06000320 V3 EN
Figure 216:
Residual current measurement
One difficulty with this solution is that the current transformer ratio is normally so
large so that the secondary residual current will be very small. The false residual
Section 10
1MRK 502 071-UEN -
Voltage protection
432
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual