Set value
Mode
Formula used for complex power calculation
L1
*
1
1
3
L
L
S
U
I
= ×
×
EQUATION1703 V1 EN
(Equation 219)
L2
*
2
2
3
L
L
S
U
I
= ×
×
EQUATION1704 V1 EN
(Equation 220)
L3
*
3
3
3
L
L
S
U
I
= ×
×
EQUATION1705 V1 EN
(Equation 221)
The function has two stages that can be set independently.
With the parameter
OpMode1(2)
the function can be set
On
/
Off
.
The function gives trip if the power component in the direction defined by the setting
Angle1(2)
is smaller than the set pick up power value
Power1(2)
Operate
Angle1(2)
Power1(2)
P
Q
en06000441.vsd
IEC06000441 V1 EN
Figure 196:
Underpower mode
The setting
Power1(2)
gives the power component pick up value in the
Angle1(2)
direction. The setting is given in p.u. of the generator rated power, see equation
.
Minimum recommended setting is 0.2% of S
N
when metering class CT inputs into the
IED are used.
1MRK 502 071-UEN -
Section 9
Current protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
379
Application manual