Only SMAI or 3PHSUM blocks shall be connected to PMU PHASORREPORT
blocks and they shall have the same cycle time, 0.9 ms.
shows an example of correct connection of SMAI and PHASORREPORT
blocks in ACT where both function blocks are working on 0.9 ms cycle time.
IEC140000124-2-en.vsd
IEC140000124 V2 EN
Figure 44:
An example of correct connection of SMAI and PHASORREPORT
blocks in ACT
shows an example of wrong connection of SMAI and PHASORREPORT
blocks in ACT where the SMAI block is working on 3 ms while PHASORREPORT
block is working on 0.9 ms cycle time.
IEC140000125-2-en.vsd
IEC140000125 V2 EN
Figure 45:
An example of wrong connection of SMAI and PHASORREPORT
blocks in ACT
Violation of rule 1 results in PMU applications not running at all. The reason is the
inconsistent cycle time. For example, in Figure
, the SMAI block is updating its
output every 3 ms while the PHASORREPORT block is expecting input every 0.9 ms.
The PHASORREPORT filtering window is designed to receive updated input every
0.9 ms and therefore the application will fail.
Rule 2:
The same SMAI or 3PHSUM block can be connected to more than one
PHASORREPORT block only if all the connected PHASORREPORT blocks have
similar instance number or only if all the connected PHASORREPORT blocks have
similar settings for SvcClass and ReportRate. Figure
PMUREPORT function block demonstrated by PCM600 Parameter Setting Tool
(PST).
Section 6
1MRK 502 071-UEN -
Wide area measurement system
116
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...