OpenCT
: Open CT detected
•
OpenCTAlarm
: Alarm issued after the setting delay
•
OpenCTIN
: Open CT in CT group inputs (1 for input 1 and 2 for input 2)
•
OpenCTPH
: Open CT with phase information (1 for phase L1, 2 for phase L2, 3
for phase L3)
7.3.3.5
Other additional options
HarmDistLimit
: This setting is the total harmonic distortion (2
nd
and 5
th
harmonic) for
the harmonic restrain pick-up. The default limit 10% can be used in normal cases. In
special application, for example, close to power electronic converters, a higher setting
might be used to prevent unwanted blocking.
TempIdMin
: If the binary input raise pick-up (DESENSIT) is activated the operation
level of
IdMin
is increased to the
TempIdMin
.
Section 1
Operate
conditionally
UnrestrainedLimit
Section 2
Section 3
Restrain
Operate
unconditionally
5
4
3
2
1
0
0
1
2
3
4
5
IdMin
EndSection1
EndSection2
restrain current
[ times IBase ]
operate current
[ times IBase ]
SlopeSection2
SlopeSection3
en06000637.vsd
TempIdMin
IEC06000637 V2 EN
Figure 71:
The value of TempIdMin
AddTripDelay
: If the input DESENSIT is activated the operation time of the
protection function can also be increased by the setting
AddTripDelay
.
OperDCBiasing
: If enabled the DC component of the differential current will be
included in the bias current with a slow decay. The option can be used to increase
Section 7
1MRK 502 071-UEN -
Differential protection
174
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...