PMU's Service class (Protection or Measurement), Phasor representation (polar or
rectangular) and the data types for phasor data, analog data and frequency data.
Synchrophasor data can be reported to up to 8 clients over TCP and/or 6 UDP group
clients for multicast or unicast transmission of phasor data from the IED. More
information regarding synchrophasor communication structure and TCP/UDP
configuration is available in section
C37.118 Phasor Measurement Data Streaming
Multiple PMU functionality can be configured in the IED, which can stream out same
or different data at different reporting rates or different performance (service) classes.
There are 2 instances of PMU functionality available in the IED. Each instance of
PMU functionality includes a set of PMU reporting function blocks tagged by the
same instance number (1 or 2). As shown in the following figures, each set of PMU
reporting function blocks includes PMUREPORT, PHASORREPORT1-4,
ANALOGREPORT1-3, and BINARYREPORT1-3 function blocks. In general, each
instance of PMU functionality has 32 configurable phasor channels
(PHASORREPORT1–4 blocks), 24 analog channels (ANALOGREPORT1-3
blocks), and 28 digital channels (24 digital-report channels in BINARYREPORT1-3
and 4 trigger-report channels in PMUREPORT function block). Special rules shall be
taken into account in PCM600 for Application Configuration and Parameter Settings
of multiple PMUREPORT blocks. These rules are explained in the the Application
Manual in section
PMU Report Function Blocks Connection Rules
shows both instances of the PMUREPORT function block. As seen, each
PMUREPORT instance has 4 predefined binary input signals corresponding to the
Bits 03-00: Trigger Reason defined in STAT field of the Data frame in IEEE
C37.118.2 standard. These are predefined inputs for Frequency Trigger, Rate of
Change of Frequency trigger, Magnitude High and Magnitude Low triggers.
IEC140000118-2-en.vsd
IEC140000118 V2 EN
Figure 39:
Multiple instances of PMUREPORT function block
shows both instances of the PHASORREPORT function blocks. The
instance number is visible in the bottom of each function block. For each instance,
there are four separate PHASORREPORT blocks including 32 configurable phasor
channels (8 phasor channels in each PHASORREPORT block). Each phasor channel
can be configured as a 3-phase (symmetrical components positive/negative/zero) or
single-phase phasor (L1/L2/L3).
Section 6
1MRK 502 071-UEN -
Wide area measurement system
108
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...