DCCLTR (A1A2)
DCCLTR (B1B2)
BC12CLTR (sect.2)
VPDCTR (A1A2)
VPDCTR (B1B2)
VPBC12TR (sect.2)
EXDU_DC (A1A2)
EXDU_DC (B1B2)
EXDU_BC (sect.2)
&
BC_12_CL
VP_BC_12
EXDU_BC
en04000485.vsd
&
&
IEC04000485 V1 EN
Figure 251:
Signals to a bus-coupler bay in section 1 from a bus-coupler bay in
another section
For a bus-coupler bay in section 2, the same conditions as above are valid by changing
section 1 to section 2 and vice versa.
15.3.3.5
Configuration setting
If there is no bypass busbar and therefore no QB2 and QB7 disconnectors, then the
interlocking for QB2 and QB7 is not used. The states for QB2, QB7, QC71 are set to
open by setting the appropriate module inputs as follows. In the functional block
diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
•
QB2_OP = 1
•
QB2_CL = 0
•
QB7_OP = 1
•
QB7_CL = 0
•
QC71_OP = 1
•
QC71_CL = 0
If there is no second busbar B and therefore no QB2 and QB20 disconnectors, then the
interlocking for QB2 and QB20 are not used. The states for QB2, QB20, QC21,
BC_12, BBTR are set to open by setting the appropriate module inputs as follows. In
the functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
•
QB2_OP = 1
•
QB2_CL = 0
•
QB20_OP = 1
•
QB20_CL = 0
•
QC21_OP = 1
•
QC21_CL = 0
1MRK 502 071-UEN -
Section 15
Control
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
525
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...