12.1.3.2
Negative sequence overcurrent protection
Example will be given how to use one CVGAPC function to provide negative
sequence inverse time overcurrent protection for a generator with capability constant
of 20s, and maximum continuous negative sequence rating of 7% of the generator
rated current.
The capability curve for a generator negative sequence overcurrent protection, often
used world-wide, is defined by the ANSI standard in accordance with the following
formula:
2
op
NS
r
k
t
I
I
=
æ
ö
ç
÷
è
ø
EQUATION1372 V1 EN
(Equation 249)
where:
t
op
is the operating time in seconds of the negative sequence overcurrent IED
k
is the generator capability constant in seconds
I
NS
is the measured negative sequence current
I
r
is the generator rated current
By defining parameter x equal to maximum continuous negative sequence rating of
the generator in accordance with the following formula
7% 0, 07
x
pu
=
=
EQUATION1373 V1 EN
(Equation 250)
can be re-written in the following way without changing the value for
the operate time of the negative sequence inverse overcurrent IED:
2
2
1
op
NS
r
k
x
t
I
x I
×
=
æ
ö
ç
÷
×
è
ø
EQUATION1374 V1 EN
(Equation 251)
In order to achieve such protection functionality with one CVGAPC functions the
following must be done:
1MRK 502 071-UEN -
Section 12
Multipurpose protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
453
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...