A safety margin of 5% for the maximum static inaccuracy and a safety margin of 5%
for maximum possible transient overreach have to be introduced. An additional 20%
is suggested due to inaccuracy of instrument transformers under transient conditions
and inaccuracy in the system data.
The minimum primary current setting (Is) is:
I
s
= 1.3 ×
I
min
EQUATION285 V3 EN
(Equation 188)
In case of parallel lines with zero sequence mutual coupling a fault on the parallel line,
as shown in Figure
, should be calculated.
IEC09000025-1-en.vsd
~
~
Z
A
Z
B
Z
L1
A
B
I
M
Fault
IED
Z
L2
M
C
Line 1
Line 2
IEC09000025 V1 EN
Figure 179:
Two parallel lines. Influence from parallel line to the through fault
current: I
M
The minimum theoretical current setting (Imin) will in this case be:
I m in
M A X I
fA
I
fB
I
M
,
,
(
)
³
EQUATION287 V1 EN
(Equation 189)
Where:
I
fA
and I
fB
have been described for the single line case.
Considering the safety margins mentioned previously, the minimum setting (Is) is:
I
s
= 1.3 ×
I
min
EQUATION288 V3 EN
(Equation 190)
The IED setting value
IN>>
is given in percent of the primary base current value,
IBase. The value for
IN>>
is given by the formula:
1MRK 502 071-UEN -
Section 9
Current protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
337
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...