XHiLim
: High limit. Set as % of
YBase
(Y is
SBase
for S,P,Q
UBase
for Voltage
measurement and
IBase
for current measurement).
XLowLim
: Low limit. Set as % of
YBase
(Y is
SBase
for S,P,Q
UBase
for Voltage
measurement and
IBase
for current measurement).
XLowLowLim
: Low-low limit. Set as % of
YBase
(Y is
SBase
for S,P,Q
UBase
for
Voltage measurement and
IBase
for current measurement).
XLimHyst
: Hysteresis value in % of range and is common for all limits.
All phase angles are presented in relation to defined reference channel. The parameter
PhaseAngleRef
defines the reference.
Calibration curves
It is possible to calibrate the functions (CVMMXN, CMMXU, VMMXU and
VNMMXU) to get class 0.5 presentations of currents, voltages and powers. This is
accomplished by amplitude and angle compensation at 5, 30 and 100% of rated
current and voltage. The compensation curve will have the characteristic for
amplitude and angle compensation of currents as shown in figure
first phase will be used as reference channel and compared with the curve for
calculation of factors. The factors will then be used for all related channels.
IEC05000652 V2 EN
Figure 308:
Calibration curves
Section 17
1MRK 502 071-UEN -
Monitoring
628
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...