Reverse zone
The reverse zone that is normally used in the communication schemes for functions
like fault current reversal logic, weak-in-feed logic or issuing carrier send in blocking
scheme must detect all faults in the reverse direction which is detected in the opposite
IED by the overreaching zone 2. The maximum reach for the protection in the opposite
IED can be achieved with the series capacitor in operation.
The reactive reach can be set according to the following formula: X1=1.3·
(X1
2Rem
-0.5(X1
L
-X
C
))
Settings of the resistive reaches are according to the minimum load impedance:
Optional higher distance protection zones
When some additional distance protection zones (zone 4, for example) are used they
must be set according to the influence of the series capacitor.
8.3.4.6
Setting of zones for parallel line application
Parallel line in service – Setting of zone 1
With reference to section
, the zone reach can be set to 85%
of the protected line.
However, influence of mutual impedance has to be taken into account.
Parallel line in service – setting of zone 2
Overreaching zones (in general, zones 2 and 3) must overreach the protected circuit in
all cases. The greatest reduction of a reach occurs in cases when both parallel circuits
are in service with a single phase-to-earth fault located at the end of a protected line.
The equivalent zero sequence impedance circuit for this case is equal to the one in
figure
.
The components of the zero sequence impedance for the overreaching zones must be
equal to at least:
R
0E
R
0
R
m0
+
=
EQUATION553 V1 EN
(Equation 129)
X
0E
X
0
X
m0
+
=
EQUATION554 V1 EN
(Equation 130)
Check the reduction of a reach for the overreaching zones due to the effect of the zero
sequence mutual coupling. The reach is reduced for a factor:
0
0 1
2 1
0
m
f
Z
K
Z
Z
R
= -
×
+
+
EQUATION1426 V1 EN
(Equation 131)
Section 8
1MRK 502 071-UEN -
Impedance protection
254
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...