txMin
: Minimum operate time for all inverse time characteristics. At high currents the
inverse time characteristic might give a very short operation time. By setting this
parameter the operation time of the step can never be shorter than the setting. Setting
range: 0.000 - 60.000s in steps of 0.001s.
IxMult
: Multiplier for scaling of the current setting value. If a binary input signal
ENMULTx (enableMultiplier) is activated the current operation level is increased by
this setting constant. Setting range: 1.0-10.0
IMinx
Operate time
Current
tx
txMin
IEC10000058
IEC10000058 V2 EN
Figure 173:
Minimum operate current and operate time for inverse time
characteristics
In order to fully comply with the definition of the curve, the setting parameter
txMin
shall be set to a value equal to the operating time of the selected inverse curve for
twenty times the set current pickup value. Note that the operate time is dependent on
the selected time multiplier setting
kx
.
ResetTypeCrvx
: The reset of the delay timer can be made as shown in Table
Table 35:
Reset possibilities
Curve name
Curve index no.
Instantaneous
1
IEC Reset (constant time)
2
ANSI Reset (inverse time)
3
The delay characteristics are described in
Technical manual
. There are some
restrictions regarding the choice of the reset delay.
For the definite time delay characteristics, the possible delay time setting
instantaneous (1) and IEC (2 = set constant time reset).
1MRK 502 071-UEN -
Section 9
Current protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
329
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...