U
ref
I
dir
IEC09000636_2_vsd
1
2
2
3
4
IEC09000636 V2 EN
Figure 172:
Directional function characteristic
1. RCA = Relay characteristic angle
2. ROA = Relay operating angle
3. Reverse
4. Forward
9.2.3.1
Settings for each step
x
means step 1, 2, 3 and 4.
DirModex
: The directional mode of step
x
. Possible settings are
Off
/
Non-directional
/
Forward
/
Reverse
.
Characteristx
: Selection of time characteristic for step
x
. Definite time delay and
different types of inverse time characteristics are available according to Table
.
1MRK 502 071-UEN -
Section 9
Current protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
327
Application manual