Table 12:
Trip LED (red)
LED state
Description
Off
Normal operation.
On
A protection function has tripped. An indication message is displayed if the
auto-indication feature is enabled in the local HMI.
The trip indication is latching and must be reset via communication, LHMI or
binary input on the LEDGEN component. To open the reset menu on the
LHMI, press
.
Flasing
Configuration mode.
Alarm indicators
The 15 programmable three-color LEDs are used for alarm indication. An individual
alarm/status signal, connected to any of the LED function blocks, can be assigned to
one of the three LED colors when configuring the IED.
Table 13:
Alarm indications
LED state
Description
Off
Normal operation. All activation signals are off.
On
•
Follow-S sequence: The activation signal is on.
•
LatchedColl-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
•
LatchedAck-F-S sequence: The indication has been acknowledged, but the
activation signal is still on.
•
LatchedAck-S-F sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
•
LatchedReset-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
Flashing
•
Follow-F sequence: The activation signal is on.
•
LatchedAck-F-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
•
LatchedAck-S-F sequence: The indication has been acknowledged, but the
activation signal is still on.
5.4.2
Parameter management
The LHMI is used to access the relay parameters. Three types of parameters can be
read and written.
•
Numerical values
•
String values
•
Enumerated values
Numerical values are presented either in integer or in decimal format with minimum
and maximum values. Character strings can be edited character by character.
Enumerated values have a predefined set of selectable values.
Section 5
1MRK 502 071-UEN -
Local HMI
100
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...