Section 3
Configuration
3.1
Description of REG670
3.1.1
Introduction
3.1.1.1
Description of configuration A20
REG670 A20 configuration is used in applications where only generator protection
within one IED is required. REG670 A20 is always delivered in 1/2 of 19" case size.
Thus only 12 analogue inputs are available. This configuration includes generator low
impedance, differential protection and all other typically required generator
protection functions. Note that 100% stator earth fault function and Pole Slip
protection function are optional.
REG670 A20 functional library includes additional functions, which are not
configured, such as additional Overcurrent protection, additional Multipurpose
protection functions, Synchronizing function, and so on. It is as well possible to order
optional two-winding transformer differential or high impedance differential
protection functions which than can be used instead of basic low-impedance generator
differential protection. Note that REG670 A20 must be re-configured if any additional
or optional functions are used.
1MRK 502 071-UEN -
Section 3
Configuration
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
57
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...