L1
IL
1
IL
2
IL
3
L2
L3
Protected Object
CT 800/1
Star Connected
IL1
IL2
IL3
IED
IEC11000026-4-en.vsdx
4
1
2
3
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AI N
5
IN
IEC11000026 V4 EN
Figure 19:
Star connected three-phase CT set with its star point away from the protected object
In the example, everything is done in a similar way as in the above described example
(Figure
). The only difference is the setting of the parameter
CTStarPoint
of the
used current inputs on the TRM (item 2 in Figure
):
•
CTprim
=600A
•
CTsec
=5A
•
CTStarPoint
=FromObject
The ratio of the first two parameters is only used inside the IED. The third parameter
as set in this example will negate the measured currents in order to ensure that the
currents are measured towards the protected object within the IED.
A third alternative is to have the residual/neutral current from the three-phase CT set
connected to the IED as shown in Figure
Section 4
1MRK 502 071-UEN -
Analog inputs
74
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual