IBase
: The parameter
IBase
is set to the generator rated current according to
.
3
N
N
S
IBase
U
=
×
EQUATION1816 V1 EN
(Equation 240)
UBase
: The parameter
UBase
is set to the generator rated Voltage (phase-phase) in
kV.
9.14.3.4
Overcurrent protection with undervoltage seal-in
To obtain this functionality, the IED application configuration shall include a logic in
accordance to figure
and, of course, the relevant three-phase generator currents
and voltages shall be connected to VRPVOC. Let us assume that, taking into account
the characteristic of the generator, the excitation system and the short circuit study, the
following settings are required:
•
Start current of the overcurrent stage: 150% of generator rated current at rated
generator voltage;
•
Start voltage of the undervoltage stage: 70% of generator rated voltage;
•
Trip time: 3.0 s.
The overcurrent stage and the undervoltage stage shall be set in the following way:
1. Set
Operation
to
On
.
2. Set
GlobalBaseSel
to the right value in order to select the Global Base Values
Group with
UBase
and
IBase
equal to the rated phase-to-phase voltage and the
rated phase current of the generator.
3. Set
StartCurr
to the value
150
%.
4. Set
Characteristic
to
IEC Def. Time
.
5. Set
tDef_OC
to
6000.00
s, if no trip of the overcurrent stage is required.
6. Set
VDepFact
to the value
100
% in order to ensure that the start value of the
overcurrent stage is constant, irrespective of the magnitude of the generator
voltage.
7. Set
Operation_UV
to
On
to activate the undervoltage stage.
8. Set
StartVolt
to the values
70
%.
9. Set
tDef_UV
to
3.0
s.
10. Set
EnBlkLowV
to
Off
(default value) to disable the cut-off level for low-voltage
of the undervoltage stage.
The other parameters may be left at their default value.
9.15
Generator stator overload protection GSPTTR
1MRK 502 071-UEN -
Section 9
Current protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
399
Application manual
Содержание Relion REG670
Страница 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Страница 2: ......
Страница 108: ...102...
Страница 132: ...126...
Страница 324: ...318...
Страница 442: ...436...
Страница 476: ...470...
Страница 628: ...622...
Страница 718: ...712...
Страница 728: ...722...
Страница 768: ...762...
Страница 778: ...772...
Страница 779: ...773...