Instructions for the FP-6000 
Protective Relay

Instructional Literature

New Information

Description

Page

Product Overview

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Quick Start

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Specifications

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Front Panel Operation

. . . . . . . . . . . . . . . . . . . . . . . . . . 23

Setting the FP-6000

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

Installation and Wiring

 . . . . . . . . . . . . . . . . . . . . . . . . 130

Startup

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145

Application and Settings

. . . . . . . . . . . . . . . . . . . . . . . 148

Programmable Logic Application

 . . . . . . . . . . . . . . . . . 174

Data Communications

. . . . . . . . . . . . . . . . . . . . . . . . . 183

Testing and Maintenance

. . . . . . . . . . . . . . . . . . . . . . . 187

Troubleshooting

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190

Appendix

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .207

Содержание Cutler-Hammer FP-6000 Series

Страница 1: ...e New Information Description Page Product Overview 2 Quick Start 9 Specifications 18 Front Panel Operation 23 Setting the FP 6000 58 Installation and Wiring 130 Startup 145 Application and Settings 1...

Страница 2: ...e of the Eaton FP 6000 Protective Relay It is provided as a guide for authorized and qualified personnel only in the selection and application of the FP 6000 Protective Relay Please refer to the speci...

Страница 3: ...rent measuring inputs four voltage measuring inputs eight contact inputs seven contact output relays communications and a front panel user interface Based upon the firmware loaded into the flash memor...

Страница 4: ...2 P 2 50 P 3 50 R 1 50 R 2 50 R 3 50 M 1 59 M 2 59 M 1 27 M 2 27 U 1 81 U 2 81 O 1 81 O 2 81 X 1 50 X 2 50 X 3 50 A 2 27 A 1 27 A 2 59 A 1 59 52 CB 3Io IR CALC METERING V I F PF W VARS VA ENERGY DEMA...

Страница 5: ...rcurrent 50P 3 50X 3 50R 3 B Under overvoltage 27M 2 59M 2 27A 2 59A 2 C Power 32 Var 32V D Under over frequency 81U 2 810 2 E Current unbalance 46 2 F Voltage unbalance 47 2 G Neutral voltage 59N 2 H...

Страница 6: ...nput circuitry Application A Comparison of current flow with apparent state of breaker B Comparison of apparent and set phase sequence C Determination of correct voltage or current phasor relationship...

Страница 7: ...nt with Directional Supervision 67 Protection Phase Overcurrent Menu 63 51R Residual Ground Inverse Time Overcurrent with Directional Supervision 67 Protection IR Residual OC Menu 65 51V 51P2 Phase In...

Страница 8: ...T 11 RTD thermal protections based on RTD direct temperature measurements Thermal Protection menu under Protection 73 49DA 1 to 49DA 11 RTD thermal alarm based on RTD direct temperature measurements T...

Страница 9: ...XX and MP3XXX drawout designs However it differs from most Eaton IQ style panel mounts in that The panel cutout is slightly larger The enclosure is mounted from the front user side of the panel Four m...

Страница 10: ...terature Page 10 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 4 FP 6000 Simple Wye Connected Application FP 6000 100 250...

Страница 11: ...ormation visit www eaton com Instructional Literature Effective May 2008 Page 11 Instructions for the FP 6000 Protective Relay Figure 5 FP 6000 Simple Wye Connected Application with Sync Check 100 250...

Страница 12: ...iterature Page 12 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 6 FP 6000 Simple Open Delta Application FP 6000 100 250 V...

Страница 13: ...formation visit www eaton com Instructional Literature Effective May 2008 Page 13 Instructions for the FP 6000 Protective Relay Figure 7 FP 6000 Simple Open Delta Application with Sync Check FP 6000 1...

Страница 14: ...rd display unchanged Each character in the Password may be modified to any of the characters 0 9 and A Z within program mode If the password has not been changed previously press enter the password de...

Страница 15: ...functions which the user must program in order to handle the specific characteristics of your system Since only one protection setting Group is enabled we need only program the one group of protection...

Страница 16: ...o 9999 cycles 50X 1 IX IOC 2 Direction Both List Forward Reverse Both IR Residual Overcurrent 51R IR TOC Shape XTRM List IT I2T I4T FLAT MOD VERY XTRM IECA IECB IECC 51R IR TOC Reset Calc List Inst Ca...

Страница 17: ...mming consists of selecting System Config or Protection from the Setting Main list For the System Config items simply scroll to the item select with Enter vary with Up Down and select with Enter For P...

Страница 18: ...A 1 A CT Rating Steady State Maximum Transient 2 x Inom 10 A 80 x Inom 400 A for 1 sec 3 x Inom 3 A 100 x Inom 100 A for 1 sec CT Burdens 0 25 VA 5 A Nominal 0 05 VA 1 A Nominal CONTACT INPUTS TB201 2...

Страница 19: ...hield J2 3 Filter Referenced to Chassis dc input impedance 2 ohms ac Input impedance 100 kHz 100 ohms Permanent Termination Resistor ZONE INTERLOCK TB3 J3 Zone Out J3 1 Open Collector Output 4 5 V to...

Страница 20: ...1 of Nominal Aux Voltage 0 to 250 V 1 of Nominal Phase Angle for I V 0 to 360 1 at Nominal Voltage System Frequency 45 to 65 Hz 0 02 Hz Ampere Demand 0 02 to 20 per Unit 0 5 Watt Demand 0 to 4000 MW 1...

Страница 21: ...Cycles or 0 1 Whichever Is Greater 32 1 Power 1 0 to 2 Cycles or 0 1 Whichever Is Greater 32 2 Power 1 0 to 2 Cycles or 0 1 Whichever Is Greater 59A 1 Voltage Aux Over 0 5 4 0 to 2 Cycles or 0 1 Which...

Страница 22: ...withstand all ports ANSI C37 90 2 1995 RF withstand Emissions EN 50081 2 EN 50011CISPR 11 Class A CFR 47 FCC Part 15 Subpart b Class A Immunity EN 61000 6 2 ENV 61000 4 2ESD Immunity ENV 61000 4 3RF...

Страница 23: ...splay mode pushbuttons with integral LEDs 9 status LEDs 6 pushbuttons for display menu navigation a Reset pushbutton 2 pushbuttons for breaker control DB 9 communication port and a battery for trip in...

Страница 24: ...ushed again once the unit shows the Default Display screen to do its pushbutton function 4 2 3 Self Check Failure Upon initialization the FP 6000 performs a series of hardware and software checks to e...

Страница 25: ...current and voltage display screen from any display menu when the relay is in normal monitoring mode The FP 6000 has a Reset menu which is accessed by pressing the Reset pushbutton when the unit is in...

Страница 26: ...view the Boot Code and Application Code versions by selecting the Version sub menu Refer to Section 4 6 to see all status and control displays and options Refer to Section 5 for programming the contro...

Страница 27: ...ves communications on pin 3 making it a Data Set or Data Communication Equipment DSE DCE under the definitions of the RS 232 standard The FP 6000 does not use the RS 232 hardware control lines Althoug...

Страница 28: ...r modes are freely accessed and cannot change or cause operation of the relay 4 6 1 Monitor The Monitor Mode is entered by pushing the Monitor pushbutton which allows the user to view metered quantiti...

Страница 29: ...nts IA Percent IB Percent IC Percent THD L N Voltages VA Percent VB Percent VC Percent Mag THD L N Voltages VA Magnitude VB Magnitude VC Magnitude Clock Time HH MM SS Date MM DD YY Current Phasors IA...

Страница 30: ...er Quadrant diagram in Figure 12 A lagging power factor is displayed as a positive value and a leading power factor is displayed as a negative value The maximum power factor is the most lagging power...

Страница 31: ...f system current over time which can be set from 1 to 60 minutes For example if the range is set for 30 minutes the FP 6000 calculates the average current over the past 30 minutes and updates the valu...

Страница 32: ...mum Power Watt Var VA Maximum Frequency Maximum Power Factor Apparent Displacement Maximum Reset Date Time Display 9 Maximum Sub menu Table 8 Maximum Sub menu The Date and Time Stamp is also recorded...

Страница 33: ...Settings Mode has no effect on the settings The user cannot change the settings in this mode this mode is for viewing the settings only Display 10 View Settings Main Select one of the Setting Main sub...

Страница 34: ...S Thermal Current Type Therm Model User Thermal Model Type I2 Multi K 6 0 Negative Sequence Current Multiplier FLA 500 Full Load Ampere LockRotor I 300 Locked Rotor Current MaxStall Tc 1 Maximum Allow...

Страница 35: ...rent Display Protection Setting Group 1 Setting Group 2 Setting Group 3 Setting Group 4 Setting Group 1 Phase Overcurrent IX Measured OC IR Residual OC Unbalance Settings Main V Protection Aux V Prote...

Страница 36: ...Shape XTRM Reset Calc Direction Both 51X IX TOC Setting Pickup pu 50 Time Mult 1 00 50X 2 IX IOC 2 Pickup pu 2 00 Delay c 600 Direction Both 50X 1 IX IOC 1 Pickup pu 2 00 Delay c 60 Direction Both IR...

Страница 37: ...Undervoltgage 59M 1 Overvoltgage LOP Block Alarm 27M 1 Undervoltgage Phases Any One Threshold V Disable Delay 1200 59M 1 Overvoltgage Phases Any One Threshold V Disable Delay 1200 LOP Block Alarm LOP...

Страница 38: ...sable Delay c 1200 Freq Protection 81U 1 Underfreq 81O 1 Overfreq 81U 1 Underfreq Threshold Disable Delay c 60 81O 1 Overfreq Threshold Disable Delay c 60 Power Protection 32 1 Power Definition 32 1 P...

Страница 39: ...ocking Zone Interlock Trip Zone Interlock Out Zone Interlock Trip Phase or Ground Disable Direction Both Zone Interlock Out Phase or Ground Disable Direction Both Synch Check 25 Synch Check Hot Dead V...

Страница 40: ...Prot RTD1 Protection Threshold Disable Delay s 10 RTD2 Protection Threshold Disable Delay s 10 RTD3 Protection Threshold Disable Delay s 10 RTD4 Protection Threshold Disable Delay s 10 RTD5 Protectio...

Страница 41: ...m 27M 2 Under V Alarm 59A 2 Over V Alarm 27A 2 Under V Alarm 59N 2 OV Definition 59N 2 OV Alarm 81O 2 Over Freq Alm 81U 2 Under Freq Al 32 3 Pwr Definition 32 3 Power Alarm 32V 3 Var Alarm 59M 2 Over...

Страница 42: ...Disable Delay s 30 RTD2 1 Pickup Alarm Pickup Disable Delay m 30 RTD2 1 Dropout Alarm Threshold Disable Delay s 30 RTD2 2 Pickup Alarm Pickup Disable Delay m 30 RTD2 2 Dropout Alarm Threshold Disable...

Страница 43: ...ut Alarm Threshold Disable Delay s 30 RTD11 2 Pickup Alarm Pickup Disable Delay m 30 RTD11 2 Dropout Alarm Threshold Disable Delay s 30 RTD49M 1 Threshold 1Thres FLA 110 RTD49M 1 Pickup Alarm Pickup D...

Страница 44: ...ts kvar Threshold Disable Delay m 0 VAR Demand Alarm Units kvar Threshold Disable Delay m 0 VA Demand Alarm Units kVA Threshold Disable Delay m 0 Current Demand Alm Threshold Disable Delay m 0 I THD A...

Страница 45: ...No Logic Pickup No RTD Pickup No Var Pickup No Cin1 No Cin3 No Cin4 No Cin5 No Cin6 No Cin7 No Cin8 No Comm No Power Demand Window Fixed Interval m 15 Waveform Capture Records 16 16 PreTrigger 2 OSC T...

Страница 46: ...ip 3 Function OR Dropout Latched Off Delay c 0 IN1 Trip BF IN2 Unused IN3 Unused IN4 Unused Output Trip2 Monitor Off Function Disable Dropout Unlatched Off Delay c 5 IN1 Unused IN2 Unused IN3 Unused I...

Страница 47: ...r Gate 6 Logic Latch 1 Logic Latch 2 Block 50X 1 IOC Block 50X 2 IOC Block 50X 3 IOC Block 50R 1 IOC Block 50R 2 IOC Block 50R 3 IOC Block 50P 1 IOC Block 50P 2 IOC Block 50P 3 IOC Block 51P TOC Block...

Страница 48: ...Ph TOC Block Ix IOC Block Ir IOC Block Phase IOC Block I Unbal 46 Block Power 32 Desensitize Gnd TOC 51X Pickup 1 00 51R Pickup 1 00 Desensitize Ph TOC 51P 1 Pickup 2 00 51P 2 Pickup 2 00 Block Ix IO...

Страница 49: ...Var 32V 32V Trip Yes 32V Alarm Yes Shot 1 PLC Lockout Function Disable IN1 Unused IN2 Unused IN3 Unused IN4 Unused Autoreclose Block L3 ExtBlockAR Disable ExtCloseDly 10 PLC BlockAR Disable UnderVolt...

Страница 50: ...W Alarm Yes AR Block 50Q 50Q 1 Trip Yes 50Q 2 Trip Yes 50Q 3 Trip Yes AR Block Var 32V 32V Trip Yes 32V Alarm Yes Shot 3 PLC Lockout Function Disable IN1 Unused IN2 Unused IN3 Unused IN4 Unused Phase...

Страница 51: ...up Active AR Block 50X 50X 1 Trip Yes 50X 2 Trip Yes 50X 3 Trip Yes AR Block 50R 50R 1 Trip Yes 50R 2 Trip Yes 50R 3 Trip Yes AR Block 50P 50P 1 Trip Yes 50P 2 Trip Yes 50P 3 Trip Yes AR Block I Unbal...

Страница 52: ...4 Function OR Dropout UnLatched IN1 CNTL 79RUN IN2 Unused IN3 Unused IN4 Unused Programmable LED 5 Function OR Dropout UnLatched IN1 CNTL 79RUN IN2 Unused IN3 Unused IN4 Unused Programmable LED 6 Fun...

Страница 53: ...og Event Log History Log Trip Log 1 50P IOC 1 19 01 2 Relay Test 10 25 00 3 0 0 00 50P IOC 1 19 01 Display Meanings Trip Time Event 2 13 36 06 109 27 Trip Time of trip Event Cause Flt Type Set Seq Num...

Страница 54: ...utputs and setting changes The data logged for each event includes the event number event I D a time stamp and an optional 2 byte parameter The user may disable logging of any event category except a...

Страница 55: ...display gives the user access to view the version of the product s boot code and application code Total History Log Display Meanings Operate Hours 00 00 00 Number of hours of operation Power Up 0 Numb...

Страница 56: ...pushbutton can be accessed through the security door on the front panel see Figure 8 Once the Test pushbutton is activated a password screen will show up on the display The default password is 0000 P...

Страница 57: ...ates that a ground overcurrent trip condition has occurred if the 50X 1 50X 2 50R 1 50R 2 51X or 51R protective functions operate Other Trip LED The red Other Trip LED indicates that a trip condition...

Страница 58: ...shipped with a default password 0000 Every time the Password Window appears the password is initialized to 0000 If the password has not been changed or set then you simply press the Enter button to b...

Страница 59: ...password is 0000 A password of 0000 will always be accepted during the first 2 minutes after the FP 6000 is powered up See Sec 5 4 11 for changing the password Press the Enter pushbutton to advance t...

Страница 60: ...s calculated 3 wire 4CT In 4CT Ig 3 wire 5 4 1 8 2 3 wire 4th CT is independent 4CT Ig 4 wire system with 4th CT on ground con ductor PH CT Ratio CT ratio of the phase current CTs Inom to 6000 Increme...

Страница 61: ...o Seq Impendance Ang Select the zero sequence line impedance angle 0 to 90 degrees 70 5 4 1 IR Dir Cntrl Select the residual ground polarizing method Off dual 3V0 Ipol Neg Off 5 4 1 Gnd Dir V 3V0 Sour...

Страница 62: ...of the time overcurrent Reset setting See TOC Curve settings for 51P 51R and 51X elements Table 11 System Configuration continued DISPLAY SETTING DESCRIPTION SETPOINT RANGE VALUE SELECTION DEFAULT SET...

Страница 63: ...urve Phase Time Overcurrent Curve Element 2 Set tings 5 4 2 1 8 3 13 4 Shape Select curve characteristic shape IT I2T I4T FLAT MOD VERY XTRM IECA IECB IECC MOD Reset Select curve reset characteristics...

Страница 64: ...th Both 51X IX TOC Setting Fourth CT Time Overcurrent Pickup and Time Multiplier Settings 5 4 2 2 8 3 Pickup Select current pickup value in per unit values x Inom 0 02 to 4 0pu or Disable 0 01 increme...

Страница 65: ...c Select delay time in cycles 0 to 9999 cycles 1 cycle increments 60 Direction Select direction Forward Reverse Both Both 50R 2 IR IOC 2 Residual CT Overcurrent Element 2 Setting 5 4 2 2 8 3 Pickup Se...

Страница 66: ...able Alarm Delay Select LOP alarm delay in cycles 0 to 9999 cycles or disable Increments of 1 10000 disable 5 Aux V Protection Select undervoltage 27A 1 and overvoltge 59A 1 device settings DISPLAY SE...

Страница 67: ...r under power Over Under Over 32 1 Pwr Trip 5 4 2 6 Threshold Select the magnitude of the power required 0 02 to 4 00pu or Disable Disable Delay c Select delay time in cycles 0 to 65535 cycles 1 cycle...

Страница 68: ...PF Displacement Power Factor Settings 5 4 2 9 Trigger PF Select power factor to trigger on 0 50to1 00 lag 0 50to 99 lead disable 0 01pu increments Disable Reset PF Select power factor to reset on 0 5...

Страница 69: ...of 1 65 Max Dead Voltage Maximum dead voltage 1 to 150 Volts Increments of 1 3 Volt Dead Time Voltage dead time 0 to 9999 cycles 1 cycle increments 10 25 In Synch Characteristic Voltage Angle Slip Dif...

Страница 70: ...Direction Select direction Forward Reverse Both Both 46 2 I Unbal Alarm Current Unbalance Alarm Settings 5 4 2 12 5 4 2 4 Threshold Select magnitude of unbalance required either I1 or I2 0 1 to 20 0...

Страница 71: ...VT Undervoltage Alarm Setting 5 4 2 12 5 4 2 5 8 6 2 Threshold V Select magnitude of undervoltage required 10 to 250 Volts disable 1 Volt increments Disable Delay c Select delay time in cycles 0 to 99...

Страница 72: ...Trip Delay 0 to 65535c 10c 32V 2 Var Trip L3 32V 2 Var Protection Settings Direction 32V 2Var Trip Direction FWD REV Both REV Criteria 32V 2 Var Trip Criterion Under Over Under Threshold 32V 2 Var Tri...

Страница 73: ...ion Settings Function RTD Group 1 Voting Function Disable Any 1 2 11 Disable RTD1 Group 1 Member RTD1 No Yes No RTD2 Group 1 Member RTD2 No Yes No RTD3 Group 1 Member RTD3 No Yes No RTD4 Group 1 Membe...

Страница 74: ...2 Pickup Alarm L3 RTD1 2 Pickup Alarm Settings Pickup RTD 1 Alarm 2 Pickup Disable 0 to 199 C or 0 to 390 F Disable Delay min RTD 1 Alarm 2 Pickup Delay 1 to 3600 min 10 min RTD1 2 Dropout Alarm L3 RT...

Страница 75: ...TD 11 Alarm 2 Pickup Delay 1 to 3600 min 10 min RTD11 2 Dropout Alarm L3 RTD11 2 Dropout Alarm Settings Threshold RTD 11 Alarm 2 Dropout 0 to 199 C or 0 to 390 F Disable Delay min RTD 11 Alarm 2 Dropo...

Страница 76: ...nits 1 to 40 000 Disable incre ments of 1 Disable Delay m Select delay time in minutes 0 to 60 minutes increments of 1 0 VAR Demand Alarm System VAR Demand Alarm Setting 5 4 3 Units Select units for V...

Страница 77: ...EFER TO SEC Breaker Alarm Breaker alarm of operations sum of interrupting amps 5 4 3 of Operation of breaker operations based on the 52a and 52b contacts 1 to 9999 increments of 1 9999 Isum INTR Amp C...

Страница 78: ...No RTD Pickup Select thermal pickup to be logged No Yes No Var Pickup Select var pickup to be logged No Yes No Cin1 Set Cin1 event to be logged No Yes No Cin2 Set Cin2 event to be logged No Yes No Cin...

Страница 79: ...igger Comm Select how to trigger wave form capture on communication command Disable Overwrite or Lock Overwrite Table 15 Input Configuration Settings Contact Input and RTD Configuration Settings Input...

Страница 80: ...t logic input IN3 for Output Trip2 See Logic Input Options Table 18 Unused IN4 Select logic input IN4 for Output Trip2 See Logic Input Options Table 18 Unused Output Rly3 Output Relay 3 Settings 5 4 6...

Страница 81: ...ction Select logic output function for Output Alarm Rly6 OR AND NOR NAND disable OR Dropout Select relay state after trip occurs Latched unlatched off delay Unlatched Off Delay c Select delay for Rela...

Страница 82: ...le 18 Unused IN2 Select logic type for logic input 2 See Logic Input Options Table 18 Unused IN3 Select logic type for logic input 3 See Logic Input Options Table 18 Unused IN4 Select logic type for l...

Страница 83: ...t if the delay is based on cycles or seconds Cycle Second Cycle On Delay c Select timer gate on delay 0 to 9999 cycles second 1 cycle second increments 0 Off Delay c Select timer gate off delay 0 to 9...

Страница 84: ...nused IN2 Select logic type for logic input 2 See Logic Input Options Table 18 Unused IN3 Select logic type for logic input 3 See Logic Input Options Table 18 Unused IN4 Select logic type for logic in...

Страница 85: ...18 Unused IN2 Select logic type for logic input 2 See Logic Input Options Table 18 Unused IN3 Select logic type for logic input 3 See Logic Input Options Table 18 Unused IN4 Select logic type for logi...

Страница 86: ...E SETTING OPTIONS SETPOINT RANGE VALUE SELECTION Unused Unused Direct or Negated Pickup PH OC G OC IOC TOC OC All Alm Volt Freq AllProt 50X 1 50X 2 50X 3 50R 1 50R 2 50R 3 50P 2 50P 3 51P 1 51P 2 51P...

Страница 87: ...ettings 5 4 8 50X 1 Select to block the CT overcurrent 1 while in cold load condition Yes No Yes 50X 2 Select to block the CT overcurrent 2 while in cold load condition Yes No Yes 50X 3 Select to bloc...

Страница 88: ...0 5 4 9 Update Clock Press the Enter pushbutton after setting clock to update the clock Table 21 Communications DISPLAY SETTING DESCRIPTION SETPOINT RANGE VALUE SELECTION DEFAULT SETTING SELECTED VALU...

Страница 89: ...O refers to the contact inputs and output relays Choosing customized I O allows the user to freely program the contact inputs and relay outputs See Table 15 Input Configuration Settings Table 16 Outp...

Страница 90: ...hange the active setting group To set the FP 6000 to its factory default settings see Section 5 3 for details Set Ctrl This setting allows the user to select the means of control for selecting the act...

Страница 91: ...ervise the ground overcurrent elements This setting effects the characteristics of 67V and 67VIX IR Gnd Dir Cntrl This setting allows the user to select the IRGround Polarizing Method Ground direction...

Страница 92: ...nimum current limit a reverse direction may be assumed The memory voltage will be used no longer than 200 milliseconds see Figure 16 Figure 17 Negative Zero Sequence Voltage Polarized Ground Direction...

Страница 93: ...e accumulator reaches 100 For example if the current is at level 1 for 40 of the total trip time based on level 1 current then the accumulator will be at 40 If the current now changes to level 2 with...

Страница 94: ...f the CT is an 800 5 multi ratio CT connected at 600 5 then a setting of 0 7 will represent a primary current pickup of 420 A 0 7 times 600 In terms of the relay current used for bench testing use the...

Страница 95: ...put The user selects the pickup and the time multiplier of the TOC curve The available settings and setting ranges are the same as the 51P PH TOC Settings shown above The pickup settings are in per un...

Страница 96: ...current unbalance The current unbalance pickup and trip functions are reset when the positive and negative sequence current I1 and I2 drop below the Threshold setting or I2 I1 drops below the I2 I1 s...

Страница 97: ...bove the underfrequency set threshold Note Phase A voltage must be greater than 10 V for this function to oper ate 81O 1 Overfreq This is the 81O device Overfrequency setting This function consists of...

Страница 98: ...ndamental watts by the fundamental volt amperes as shown below This definition is only valid at the system fundamental operating frequency The Displacement Power Factor isolates the fundamental portio...

Страница 99: ...range and a closing command has been presented but their magnitude or angle difference has been out of their range for the specified Timeout The Sync failure flag is one of the control options for us...

Страница 100: ...the thermal threshold based on the thermal capacity TC which can be obtained with the settings Locked Rotor Current ILR and Maximum Allowable Stall Time TLR When any phase current exceeds the thermal...

Страница 101: ...ed trip output occurs VA Power Alarm Units Sets the units for VA measurement kVA or MVA Threshold Sets the VA threshold level in units specified at or above which the power pickup event occurs After p...

Страница 102: ...he Logging functions Current Demand Interval m Sets the interval in number of minutes from 1 to 60 minutes in 1 minute intervals After each specified interval the average current for that period is ca...

Страница 103: ...ts the buffer to be overwritten or locked The dV dI looks for approximately 17 change in either the voltage or current signals and can be used to record waveforms for any disturbance greater than 17 L...

Страница 104: ...h the FP 6000 it can be used for not only a motor but also a generator transformer cable and etc The FP 6000 treats all the RTD channels as general use inputs Therefore care must be taken to make sure...

Страница 105: ...energize the Breaker Trip coil The Trip1 relay is set per the settings described below Monitor Set to On or Off If set to on the Breaker Trip coil circuit will be monitored by the FP 5000 for continu...

Страница 106: ...so linked to the System Config settings which is where the total number of settings groups 1 to 4 is programmed In This setting defines the logic input to Timer Gates 1 through 6 See the settings tabl...

Страница 107: ...ct the clock setting in the Setting Main display window Configure the settings below to set the clock Date Mode Sets the mode for the date used in all time stamp displays Time Mode Sets the mode for t...

Страница 108: ...nterrupted current is less than or equal to the interrupt current at the last point the FP 6000 will interpolate the allowed operation counts based on the breaker wear curve When the interrupted curre...

Страница 109: ...40 pu 18 Count 3 Open Counts Allowed 3 1 to 0xFFFF 20 Point 4 L2 Point 4 Settings Cur 4 pu Interrupted Current Level 4 0 to 40 pu 24 Count 4 Open Counts Allowed 4 1 to 0xFFFF 15 Point 5 L2 Point 5 Set...

Страница 110: ...or disable The indicator is active when the Healthy Alarm is de energized to report a failure The default configuration sets the Dropout to Latched and enables the Trip Indication when Trip1 or Trip2...

Страница 111: ...2 See Logic Input Options Table 26 Unused Programmable LED 3 L2 Programmable LED 3 Menu Function Select Logic Output Function for LED 3 Disable OR AND NOR NAND OR Dropout Select LED 3 State After It I...

Страница 112: ...Select Logic Output Function for LED 8 Disable OR AND NOR NAND Disable Dropout Select LED 8 State After It Is Lit Unlatched Latched Unlatched IN1 Select Logic Input IN1 for LED 8 See Logic Input Opti...

Страница 113: ...P 3 51P 1 51P 2 51P 51X 51R 59A 1 59A 2 27A 1 27A 2 59M 1 59M 2 27M 1 27M 2 46 1 46 2 47 1 47 2 81U 1 31U 2 81O 1 81O 2 BF 55A 55D 55N 1 59N 2 32 1 32 2 32 3 LOP LOPB 49DTG1 49DTG2 49DT1 49DT2 48DT3 4...

Страница 114: ...ifting the trip curve left or right of the normal trip curve To coordinate with the down stream relay or recloser all shot protection groups can be based on one normal setting group or multiple groups...

Страница 115: ...an the sum of four shot breaker off times four longest protection trip times at least one Run to Ready reset time and a safety margin SyncControl Sync Supervision If it is enabled an autoreclose is pe...

Страница 116: ...to several aspects such as the circuit breaker characteristic the protection functions used the power system protected voltage level overhead or cable stability and etc and impacts on loads Set Group...

Страница 117: ...zone coordination process 51Q Pickup Shot x 51Q Pickup This setting is reserved for the 51Q negative sequence time inverse overcurrent 51P Pickup Shot x 51P Pickup This setting allows the relay to mod...

Страница 118: ...Autoreclose Failure Time T3 0 to 65535c 3000 c AR Sync Control L3 Autoreclose Sync check Supervision Enable SyncControl Sync Supervision Disable Enable Disable AutoReclose Block L3 Autoreclose Block S...

Страница 119: ...0P 2 Trip Shot 1 Block 50P 2 Yes No Accelerate 0 to 60c Yes 50P 3 Trip Shot 1 Block 50P 3 Yes No Accelerate 0 to 60c Yes AR Block I Unbal L4 Autoreclose Block Unbalance Current Functions 46 1 Trip Sho...

Страница 120: ...ickup Settings 51X Pickup Shot 2 51X Pickup 0 1 to 4 pu Disable 1 00 pu 51R Pickup Shot 2 51R Pickup 0 1 to 4 pu Disable 1 00 pu 51Q Pickup Shot 2 51Q Pickup 0 1 to 4 pu Disable 1 00 pu Phase TOC Pick...

Страница 121: ...s AR Block 50Q L4 Autoreclose Block Negative Sequence Overcur rent Functions 50Q 1 Trip Shot 3 Block 50Q 1 Yes No Accelerate 0 to 60c Yes 50Q 2 Trip Shot 3 Block 50Q 2 Yes No Accelerate 0 to 60c Yes 5...

Страница 122: ...up Shot 4 51R Pickup 0 1 to 4 pu Disable 1 00 pu 51Q Pickup Shot 4 51Q Pickup 0 1 to 4 pu Disable 1 00 pu Phase TOC Pickup L4 Phase Time Inverse Overcurrent Pickup Settings 51P Pickup Shot 4 51P Picku...

Страница 123: ...ULT SETTING Frequency 60 Phase Seq ABC CT Connect 3 wire PH CT Ratio 500 5 IX CT Ratio 500 5 VT Connect Wye VTRatio Exp 2 Main VTR 100 Aux VTR 100 VT Secondary Rating 69 28 Prim Units No I O Config De...

Страница 124: ...irection Both IX OVERCURRENT IX SETTINGS DEFAULT SETTING 51X IX TOC Shape XTRM Reset Calc Direction Both Pickup 0 50 Time Mult 1 00 50X 1 IX OC 1 Pickup 1 00 Delay c 60 Direction Both 50X 1 IX OC 2 Pi...

Страница 125: ...LOG ENABLE SETTINGS DEFAULT SETTING I Pickup Yes DATA LOGGER DATA LOGGER SETTINGS DEFAULT SETTING Mode Trigger Interval s Value 1 Value 2 Value 3 Value 4 Value 5 Value 6 Value 7 Value 8 Cont Auto 900...

Страница 126: ...ALARM SETTINGS DEFAULT SETTINGS Function Dropout IN1 IN2 IN3 IN4 OR Unlatched Trip Allprot Trip All Alarms Sys Alm All Alarm Breaker All Alm TRIP INDICATOR TRIP INDICATOR SETTINGS DEFAULT SETTING Drop...

Страница 127: ...36 Breaker Curve Configuration Default Settings BREAKER CURVE CURVE SETTINGS DEFAULT SETTING Point 1 Cur pu 6 Count 40 Point 2 Cur pu 12 Count 30 Point 3 Cur pu 18 Count 20 Point 4 Cur pu 24 Count 15...

Страница 128: ...CNTL 79Lock IN3 Unused IN4 Unused Programmable LED 2 L2 Function OR Dropout Unlatched IN1 79RUN IN2 Unused IN3 Unused IN4 Unused Programmable LED 3 L2 Function OR Dropout Unlatched IN1 79SH1 IN2 Unuse...

Страница 129: ...r the FP 6000 Protective Relay Table 37 LED Configuration Default Settings continued LED CONFIG LED SETTINGS DEFAULT SETTING Programmable LED 7 L2 Function OR Dropout Unlatched IN1 79Lock IN2 Unused I...

Страница 130: ...footprint outline is equivalent to the Eaton DT3XXX and MP3XXX draw out designs However it differs from most Eaton IQ style panel mounts in that The panel cutout is slightly larger The enclosure is mo...

Страница 131: ...n 3 18 mm thick and distortion free Insure that there are no mechanical problems that could effect the overall mounting thickness of the outer chassis from the termination back to the front of the lat...

Страница 132: ...0 rear terminal connections Connect ground terminal shown in lower left hand corner of rear panel see Figure 30 to the closest solid electrical safety grounding point with a heavy wire or braid 14 AWG...

Страница 133: ...d is not provided to the user see Figure 35 The wetting voltage and current requirements of the external contacts should be reviewed for compatibility with the FP 6000 s 40 Vdc source voltage and 2mA...

Страница 134: ...ng rules and details J2 INCOM AB this is an INCOM type interface reserved for future design features The hardware is identical to J1 accept that there is a non switch selectable 100 ohm termination re...

Страница 135: ...he case care must be taken as many electronic components and circuits are exposed Service personnel should use electrostatic wrist straps to avoid damage due to electrostatic discharge ESD Touching th...

Страница 136: ...age 136 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 34 Voltage Wye Input Wiring Options and Connection Schematics FP 60...

Страница 137: ...mation visit www eaton com Instructional Literature Effective May 2008 Page 137 Instructions for the FP 6000 Protective Relay Figure 35 Voltage Wye Input Wiring Options and Connection Schematics 100 2...

Страница 138: ...ge 138 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 36 Voltage Delta Input Wiring Options and Connection Schematics FP 6...

Страница 139: ...sit www eaton com Instructional Literature Effective May 2008 Page 139 Instructions for the FP 6000 Protective Relay Figure 37 Voltage Delta Input Wiring Options and Connection Schematics with Sync Ch...

Страница 140: ...eassembled plastic optical fibers with connectors can be ordered from Eaton Cutler Hammer or from any distributor of Agilent Technologies optical fiber products In addition these same distributors off...

Страница 141: ...ber to set the URTD module DIP switches according to the types of RTDs in each of the winding motor bearing load bearing and auxiliary groups see IL 17367 Figure 38 Universal RTD Module Mounting Dimen...

Страница 142: ...Instructional Literature Page 142 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 39 URTD Wiring to URTD Module F...

Страница 143: ...Instructional Literature Effective May 2008 Page 143 Instructions for the FP 6000 Protective Relay Figure 40 Typical ac Supply and URTD Wiring UNIVERSAL RTD MODULE J1 J2 J3 J5 J4 URTD FO OPTICAL FIBER...

Страница 144: ...Instructional Literature Page 144 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 41 Common CT Wiring Configurations 6...

Страница 145: ...125 Vdc or control power transformer 100 120 Vac De energize the power supply source For 250 Vdc power supply board nominal ranges 100 to 240 Vac or 100 to 250 Vdc Verify trip relay control voltage Co...

Страница 146: ...d read Off Verify that the healthy relay is in the energized state Removing power to the FP 6000 power supply should disengage the healthy relay closing the NC contacts TB105 which should drive an Ala...

Страница 147: ...ed by the application engineer or equipment manufacturer verify that the breaker is operating properly and the load is energized With a load on the breaker use a clamp on type ammeter to measure the a...

Страница 148: ...panel The phase angle for voltages and currents is computed from the one cycle voltage and current phasor values every 32 cycles for updating the current phasor angle displays 8 1 2 Frequency Measurem...

Страница 149: ...l tiplier setting The ground trip time at 1 per unit current is 5 D ANSI IEC The ANSI Moderately Inverse Very Inverse and Extremely Inverse curves are defined by ANSI C37 112 The IEC curves are define...

Страница 150: ...coordination potential and permits curve shaping over a wide range The available pickup settings which are inverse time overcurrent time multiplier settings and inverse time overcurrent phase and grou...

Страница 151: ...nce The tolerances are usually stated in terms of the relay s accuracy and frequently highlighted on the actual working curves Accuracy is stated in terms of a plus or minus percentage and represents...

Страница 152: ...can be adjusted from 0 10 to 4 00 times Inom Figure 47 graphically illustrates how the beginning of the Thermal Inverse Time Overcurrent Pickup portion of the overall curve can be moved horizontally o...

Страница 153: ...stment Table 40 Negative Sequence Current Protection Settings 8 4 Curve Overlapping Issues Several calculations are performed simultaneously for the determination of trip and alarm conditions Each of...

Страница 154: ...ound then any directional permissive ground or residual current IOC or TOC pickup will cause activation of zone out signal Phase current IOC or TOC will not activate the signal If the Zone Out setpoin...

Страница 155: ...voltage unbalance pickup occurs when V2 V1 exceeds the VUB Unbalance setting and the V1 or the V2 magnitude exceeds the VUB Threshold setting The Voltage Unbalance trip is set when the pickup conditi...

Страница 156: ...the programmable logic input All the current elements can be blocked through their block gate logic and other functions may be blocked through the programmable logic if the user desires The LOP logic...

Страница 157: ...hreshold setting The overfrequency trip is set when the overfrequency condition exists for the delay time specified The overfrequency pickup and trip are reset when the frequency drops below the overf...

Страница 158: ...FP 6000 has been designed to issue a close breaker signal from one of its programmable contact outputs The default configuration maps the Close Breaker function to contact output relay 5 see Figure 5...

Страница 159: ...sensed across the Trip 1 relay output contacts whenever the breaker state is closed and the Trip 1 relay is open Since the state of the breaker must be known this function is operational only if at l...

Страница 160: ...ithout delay If after Breaker Failure Delay cycles the current is above BF Phase or BF Ground current limits then the Breaker Failure BF Trip indication is given along with the BF lockout indication B...

Страница 161: ...on 9 Programmable Logic and Section 5 Table 17 for LG6 programming is used to cause a waveform trigger This logic gate can be used to trigger on any combination of trip pickup and alarm events It is a...

Страница 162: ...Pass then a trigger will not be recognized until the data logger is reset The data logger can have its data reset in one of the following ways Front Panel Reset Press the reset button until the Reset...

Страница 163: ...al However if there is either an external lockout command or a general programmable lockout logic active or both the autoreclose logic will go to Lockout mode Figure 58 Autoreclose Control Blocking Lo...

Страница 164: ...condition exists such as External lockout command General programmable lockout logic active Autoreclose blocking timeout Autoreclose failure Breaker wear lockout Not enough breaking capacity lockout E...

Страница 165: ...logic will increment to next shot stage and wait for next reclose initiate If the fault persists the autoreclose logic will go all reclose shots allowed and eventually go into Lockout mode The reclos...

Страница 166: ...ickup or a manual remote closing is performed 2 1 0 3 4 AR Initiate Setting 52CSa52b 52b ProtTrip ProtTrip 52b PLC79RI Ext Initiate Enable 52b 79 Blocking 79 Lockout 52CSa Protection Trip S R Q 5c 0 P...

Страница 167: ...ble Current Max Shots Setting Run S R Q Lockout Max_Shot Breaker Wear Lockout AR Block Timeout Breaker Not Enough Capacity External Lockout PLC SH1 3 Lockout 79RL Reset AR Lockout T4 10c 52a OC Pickup...

Страница 168: ...es may be enabled or disabled If the maximum shots per hour feature is disabled there will be no time limit on how many shots can be performed If the maximum shot adjustment feature is enabled the max...

Страница 169: ...pumping logic the autoreclose logic will switch the settings from the shot protection settings to the normal settings after the Run to Ready timer is expired but it will not reset from Run mode to Rea...

Страница 170: ...p 8 13 Thermal Protection and Alarm The FP 6000 provides the thermal protections and alarms that are based on the direct temperature measurement through the URTD device offered by Eaton Corporation an...

Страница 171: ...given the current threshold of 1 0FLA and 2 0FLA of the stator phase current the thermal model will use the full thermal capacity in 139 54 seconds However if the stator temperature is known of 100 C...

Страница 172: ...f equipment to be protected The negative sequence current will generate significantly more heat on a rotating machine but has the same effect as the positive sequence current for stationary equipment...

Страница 173: ...es the same as the MP 3000 With current harmonics the FP 6000 thermal model tends to be less sensitive Therefore depending on the nature of currents measured the thermal threshold may need to be set a...

Страница 174: ...The FP 6000 Protective Relay includes programmable logic for programming inputs outputs blocking of protective functions and custom logic functions in the relay The logic provides control of the outpu...

Страница 175: ...electromechanical output relays The relays include five Form A output relays Trip1 Trip2 Rly3 Rly4 Rly5 one Form C Alarm output relay and a Form C Relay Healthy Alarm relay The functionality of the R...

Страница 176: ...d operation See Default settings in Table 51 Table 51 LED Configuration Default Indicator Settings Note Relay K7 is always Relay Healthy It is energized when all internal diagnostics pass and de energ...

Страница 177: ...off delay timers The setting range on the timers is 0 to 9999 cycles with 1 cycle resolution The latches include a set input and a reset input The reset input has the highest priority If both the set...

Страница 178: ...c input from a particular Data Store The computed outputs of the logic elements are also saved The stored results may be directed to additional logic gate inputs until an output is directed to an outp...

Страница 179: ...8 to enable or disable the High Load Alarm at the user s discretion A Timer Gate has an On Delay and or an Off Delay that can be set for up to 9999 cycles 166 minutes at 60 Hz Use 60 cycles for an On...

Страница 180: ...direction Reverse 67X F Fourth CT fault current direction Forward 67X R Fourth CT fault current direction Reverse 67X F Fourth CT fault current direction Forward 67VIXF Fourth CT Zero sequence voltage...

Страница 181: ...Blocking flag caused by LOP condition BF Breaker failure flag 59N 1 2 Neutral or zero sequence voltage elements 32 1 2 3 Real power protection elements PhZone Phase zone interlock trip LOPA LOP Alarm...

Страница 182: ...oint Group Control is set to Local Remote the active setpoint group is selected using either a sub menu option of the Status Control PB or the PowerNet slave action command 3 D 0 The active setpoint g...

Страница 183: ...the cable leads to minimize frayed connections and add stress release Always follow the National Electrical and local codes for cable routing When leaving a building lightening surge protection is re...

Страница 184: ...el RS 232 connector on the front panel of the FP 6000 using a standard DTE to DSE cable The FP 6000 front panel RS 232 connector is wired as a 9 socket female Data Set DSE D Subminiature under the RS...

Страница 185: ...e networked location via an intranet or the Internet 10 4 3 Licensing PowerNet Software uses a floating license system to license the PowerNet Software applications Each copy of a PowerNet Software ap...

Страница 186: ...communication NetPower Monitor PowerNet Monitor is a PowerNet Software application used to monitor and control devices on PowerNet DeviceServers With PowerNet Monitor you can view all the detailed de...

Страница 187: ...ed up and protection is active If the power source goes out or if the FP 6000 senses an internal error this relay will open This is a Form C relay and the NO contact can be used for example to drive a...

Страница 188: ...nd overvoltage protection If the settings are not as desired then modify it in the setting s menu under Protection Main V Protection Set the undervoltage to 60 volts and then the overvoltage to 120 vo...

Страница 189: ...r once again to confirm With an ohmmeter measure between pins 113 and 114 of connector TB1 to verify that Relay 3 is closed The resistance should be close to zero ohms Now press the Previous button to...

Страница 190: ...hat an FP 6000 critical failure is detected the protection functions of the FP 6000 are disabled and all output relays except relay healthy will remain in their current state The relay healthy output...

Страница 191: ...ly Protection Disabled Setting Failure Settings Disabled If Fail the setpoints have been corrupted The circuit is not protected replace FP 6000 immediately Display Warning Display Enabled The display...

Страница 192: ...ing of input states and the changing of a communication driven logic variable must be enabled by programming setpoints see Section 5 The ability to ignore particular types of events is given so that e...

Страница 193: ...use SetChange The program settings are changed and saved The Setpoint Sequence number PRSetGrpCh The protection active setting group is changed The new active setting group number 1 4 SetRTC The real...

Страница 194: ...be all unbalance frequency breaker failure power factor power and zone interlocking pickups 81 OF Overfrequency has picked up or dropped out Miscellaneous Pickup Status contains the status flags that...

Страница 195: ...quency breaker failure power factor power and zone interlocking trips 81 OF Overfrequency has operated Miscellaneous Trip Status contains the status flags that describe all unbalance frequency breaker...

Страница 196: ...3 Rly4 Rly5 or Alarm has changed state Output Status contains the status flag for all contact outputs Healthy State The Relay Healthy contact output has changed state Output Status contains the status...

Страница 197: ...ring after the event has been cleared the FP 6000 Active Alarm setting must be set to Unlatched To do this simply press Set enter the password scroll to Output Config and press Enter Scroll to Alarm I...

Страница 198: ...the FP 6000 Scroll to the History Log and press Enter Scroll to Bkr History and press the Enter pushbutton two times LOP ALARM Condition must be cleared externally away from the FP 6000 unit CONDITION...

Страница 199: ...taneous Over Current operation 50R IOC A Residual current Instantaneous Over Current operation 50X IOC An IX ground current Instantaneous Over Current operation 51P TOC A Phase current Time Over Curre...

Страница 200: ...Status A group of status flags detailing miscellaneous protective function pickups at the time of the trip 18 OC Trip Status A group of status flags detailing Over Current protective function operati...

Страница 201: ...on of the firmware This S Record file contains all the information necessary to upgrade your FP 6000 firmware The FlashLoader program must be installed on your PC and your PC must have RS 232 serial c...

Страница 202: ...in the RAM This command should ONLY be used when upgrading the firmware Eaton recommends executing this command before and after the firmware has been updated Before you execute this command make sur...

Страница 203: ...en S Record File Figure 83 Flash Loader Open the selected file Once this has been accomplished this screen will automatically close and the next screen will appear asking the user to verify the select...

Страница 204: ...he Enter Flash Load Mode pushbutton switches the relay from normal mode to flash load mode see Figure 87 Figure 87 Flash Programmer The recommended procedure is to first erase the memory by pushing th...

Страница 205: ...structions to Click Program to download the application code see Figure 90 Figure 90 Flash Program Operation The FP 6000 will display Flash Loader Mode BlankCheck Pass A complete bar will appear at th...

Страница 206: ...se the FP 6000 and reprogram following the above steps 12 4 5 Upgrading Firmware Upgrading Phase 1 firmware Version 1 0 or 1 03 to Phase 2 or later will not be possible directly A two step process mus...

Страница 207: ...Frequency Shift Keying is encoding typically used by a MODEM HMI Human Machine Interface is also called MMI or Man Machine Interface Ia Ib Ic Phase currents for phases a b and c respectively Icon A pi...

Страница 208: ...ciated current samples taken 90 earlier Thus a leading power factor will follow the convention of being positive Real Power Watts Real power is computed by summing the product of the individual curren...

Страница 209: ...s below a programmed value 32 Power Protection Functions on a desired value of power flow in a given direction or upon reverse power 46 Reverse Phase or Phase Balance Current Relay Relay which functio...

Страница 210: ...008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E 13 4 Time Current Curves A variety of inverse time overcurrent curves for the FP 6000 are shown i...

Страница 211: ...IB02602004E For more information visit www eaton com Instructional Literature Effective May 2008 Page 211 Instructions for the FP 6000 Protective Relay Figure 95 ANSI Very Inverse...

Страница 212: ...Instructional Literature Page 212 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 96 ANSI Extremely Inverse...

Страница 213: ...IB02602004E For more information visit www eaton com Instructional Literature Effective May 2008 Page 213 Instructions for the FP 6000 Protective Relay Figure 97 IEC A...

Страница 214: ...Instructional Literature Page 214 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 98 IEC B...

Страница 215: ...IB02602004E For more information visit www eaton com Instructional Literature Effective May 2008 Page 215 Instructions for the FP 6000 Protective Relay Figure 99 IEC C...

Страница 216: ...Instructional Literature Page 216 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 100 IEC...

Страница 217: ...IB02602004E For more information visit www eaton com Instructional Literature Effective May 2008 Page 217 Instructions for the FP 6000 Protective Relay Figure 101 ANSI...

Страница 218: ...Instructional Literature Page 218 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 102 Thermal...

Страница 219: ...IB02602004E For more information visit www eaton com Instructional Literature Effective May 2008 Page 219 Instructions for the FP 6000 Protective Relay Figure 103 Phase I4t...

Страница 220: ...Instructional Literature Page 220 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 104 I2t...

Страница 221: ...IB02602004E For more information visit www eaton com Instructional Literature Effective May 2008 Page 221 Instructions for the FP 6000 Protective Relay Figure 105 It...

Страница 222: ...Instructional Literature Page 222 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 106 Ground I4t...

Страница 223: ...IB02602004E For more information visit www eaton com Instructional Literature Effective May 2008 Page 223 Instructions for the FP 6000 Protective Relay Figure 107 Ground I2t...

Страница 224: ...Instructional Literature Page 224 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Figure 108 Ground IT...

Страница 225: ...thstand to 35 V M 27 1000 MHz UL CUL FP 6000 UL Compliance is covered under UL File Number E154862 Catalog FP 6000 00 5 Amp Version only FP5100 00 1 Amp version pending UL 1053 Ground Fault Interrupti...

Страница 226: ...Instructional Literature Page 226 Effective May 2008 Instructions for the FP 6000 Protective Relay For more information visit www eaton com IB02602004E Notes...

Страница 227: ...IB02602004E For more information visit www eaton com Instructional Literature Effective May 2008 Page 227 Instructions for the FP 6000 Protective Relay Notes...

Страница 228: ...poration All Rights Reserved Printed in USA Publication No IB02602004E TBG00196 May 2008 Instructions for the FP 6000 Protective Relay Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon...

Отзывы: