Table 55. Control Option Definitions.
CONTROL OPTION
DESCRIPTION
Open Bkr
A command to open breaker.
Close Bkr
A command to close breaker.
Open
A flag to indicate that breaker is open.
Closed
A flag to indicate the the breaker is closed.
BkFailAlm
Breaker failure alarm flag.
StateAlm
Breaker status disagreeement alarm.
Mntr1Alm
Trip coil broken alarm.
Mntr2Alm
Close coil broken alarm.
AllAlm
All alarm flag.
67G-F
Ground fault direction: Forward.
67G-R
Ground fault direction: Reverse.
67V-F
Zero sequence voltage polarized fault direction: Forward.
67V-R
Zero sequence voltage polarized fault direction: Reverse.
67Q-F
Negative sequence voltage polarized fault direction: Forward.
67Q-R
Negative sequence voltage polarized fault direction: Reverse.
67I-F
Neutral current polarized fault direction: Forward.
67I-R
Neutral current polarized fault direction: Reverse.
67X-F
Fourth CT fault current direction: Forward.
67X-R
Fourth CT fault current direction: Reverse.
67X-F
Fourth CT fault current direction: Forward.
67VIXF
Fourth CT Zero sequence voltage polarized fault current direction: Forward.
67VIXR
Fourth CT Zero sequence voltage polarized fault current direction: Reverse.
67A-F
Phase A current direction: Forward.
67B-F
Phase B current direction: Forward.
67C-F
Phase C current direction: Forward.
SynchFail
Synch fail alarm.
SlipAlm
Frequency difference between tow voltage sources is out of range.
25BL
Bus voltage normal.
25LL
Line voltage normal.
ColdLoad
In cold load condition (load is energized after a specified time of outage with inrush current).
79RUN
Autoreclose RUN mode.
79BLCK
Autoreclose process is blocked in either READY or RUN mode.
79Lock
Autoreclose LOCKOUT mode.
79Fail
Autoreclose logic time out.
79SH1
Autoreclose logic is at shot 1 stage in RUN mode.
79SH2
Autoreclose logic is at shot 2 stage in RUN mode.
79SH3
Autoreclose logic is at shot 3 stage in RUN mode.
79SH4
Autoreclose logic is at shot 4 stage in RUN mode.
79AntiP
Breaker pumping condition is identified and the autoreclose logic is in anti-pumping process.