IB02602004E
For more information visit: www.eaton.com
Instructional Literature
Effective: May 2008
Page
121
Instructions for the FP-6000 Protective Relay
Table 27. AR Settings: Select the AR Settings (continued).
DISPLAY SETTING
DESCRIPTION
SETTING RANGE /
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
AR Block 50R (L4)
Autoreclose Block 50R Overcurrent Functions
50R-1 Trip
Shot 3 Block 50R-1
Yes, No, Accelerate (0 to 60c)
Yes
50R-2 Trip
Shot 3 Block 50R-2
Yes, No, Accelerate (0 to 60c)
Yes
50R-3 Trip
Shot 3 Block 50R-3
Yes, No, Accelerate (0 to 60c)
Yes
AR Block 50P (L4)
Autoreclose Block 50P Overcurrent Functions
50P-1 Trip
Shot 3 Block 50P-1
Yes, No, Accelerate (0 to 60c)
Yes
50P-2 Trip
Shot 3 Block 50P-2
Yes, No, Accelerate (0 to 60c)
Yes
50P-3 Trip
Shot 3 Block 50P-3
Yes, No, Accelerate (0 to 60c)
Yes
AR Block I Unbal (L4)
Autoreclose Block Unbalance Current Functions
46-1 Trip
Shot 3 Block 46-1
Yes, No, Accelerate (0 to 60c)
Yes
46-2 Trip
Shot 3 Block 46-2
Yes, No, Accelerate (0 to 60c)
Yes
Ground TOC Pickup (L4)
Ground Time Inverse Overcurrent Pickup Settings
51X Pickup
Shot 3 51X Pickup
0.1 to 4 pu, Disable
1.00 pu
51R Pickup
Shot 3 51R Pickup
0.1 to 4 pu, Disable
1.00 pu
51Q Pickup
Shot 3 51Q Pickup
0.1 to 4 pu , Disable
1.00 pu
Phase TOC Pickup (L4)
Phase Time Inverse Overcurrent Pickup Settings
51P Pickup
Shot 3 51P Pickup
0.1 to 4 pu , Disable
2.00 pu
51P2 Pickup
Shot 3 51P2 Pickup
0.1 to 4 pu , Disable
Disable
AR Block Power 32W (L4)
Autoreclose Block Power Functions
32W Trip
Shot 3 Block 32W Trip
Yes, No
Yes
32W Alarm
Shot 3 Block 32W Alarm
Yes, No
Yes
AR Block 50Q (L4)
Autoreclose Block Negative Sequence Overcur-
rent Functions
50Q-1 Trip
Shot 3 Block 50Q-1
Yes, No, Accelerate (0 to 60c)
Yes
50Q-2 Trip
Shot 3 Block 50Q-2
Yes, No, Accelerate (0 to 60c)
Yes
50Q-3 Trip
Shot 3 Block 50Q-3
Yes, No, Accelerate (0 to 60c)
Yes
AR Block Var 32V (L4)
Autoreclose Block Var Functions
32V Trip
Shot 3 Block 32V Trip
Yes, No
Yes
32V Alarm
Shot 3 Block 32V Alarm
Yes, No
Yes
Shot 3 PLC Lockout (L4)
Shot 3 Programmable Lockout Logic Gate Settings
Function
Shot 3 PLC to Lockout
Disable, OR, AND, NOR, NAND
Disable
IN1
Shot 3 PLC to Lockout IN1
See Logic Input Options Table 26
IN2
Shot 3 PLC to Lockout IN2
See Logic Input Options Table 26
IN3
Shot 3 PLC to Lockout IN3
See Logic Input Options Table 26
IN4
Shot 3 PLC to Lockout IN4
See Logic Input Options Table 26
Shot 4 Prot Setting (L4)
Shot 4 Protection Settings
SH 4 Offtime&SetGrp (L4)
Shot 4 Breaker Off Time and Set Group
SH1 OffTime
Shot 4 Breaker Off Time T21
0 to 65535c
30c
Set Group
Shot 4 Protection Set Group
Active, 1, 2, 3, 4
Active = 0
AR Block 50X (L4)
Autoreclose Block 50X Overcurrent Functions
50X-1 Trip
Shot 4 Block 50X-1
Yes, No, Accelerate (0 to 60c)
Yes
50X-2 Trip
Shot 4 Block 50X-2
Yes, No, Accelerate (0 to 60c)
Yes
50X-3 Trip
Shot 4 Block 50X-3
Yes, No, Accelerate (0 to 60c)
Yes
AR Block 50R (L4)
Autoreclose Block 50R Overcurrent Functions
50R-1 Trip
Shot 4 Block 50R-1
Yes, No, Accelerate (0 to 60c)
Yes
50R-2 Trip
Shot 4 Block 50R-2
Yes, No, Accelerate (0 to 60c)
Yes
50R-3 Trip
Shot 4 Block 50R-3
Yes, No, Accelerate (0 to 60c)
Yes
AR Block 50P (L4)
Autoreclose Block 50P Overcurrent Functions
50P-1 Trip
Shot 4 Block 50P-1
Yes, No, Accelerate (0 to 60c)
Yes
50P-2 Trip
Shot 4 Block 50P-2
Yes, No, Accelerate (0 to 60c)
Yes
50P-3 Trip
Shot 4 Block 50P-3
Yes, No, Accelerate (0 to 60c)
Yes