Instructions for the FP-6000 Protective Relay
50P-1 Trip
Shot x Block 50P-1. This setting allows the relay to block or
unblock 50P-1 phase instantaneous overcurrent function or
modify its delay during shot x. The same criteria as 50X-1 Trip.
50P-2 Trip
Shot x Block 50P-2. This setting allows the relay to block or
unblock 50P-1 phase instantaneous overcurrent function or
modify its delay during shot x. The same criteria as 50X-1 Trip.
50P-3 Trip
Shot x Block 50P-3. This setting allows the relay to block or
unblock 50P-1 phase instantaneous overcurrent function or
modify its delay during shot x. The same criteria as 50X-1 Trip.
46-1 Trip
Shot x Block 46-1. This setting allows the relay to block or
unblock 46-1 current unbalance protection or modify its delay
during shot x. The same criteria as 50X-1 Trip.
46-2 Trip
Shot x Block 46-2. This setting allows the relay to block or
unblock 46-2 current unbalance protection or modify its delay
during shot x. The same criteria as 50X-1 Trip.
51X Pickup
Shot x 51X Pickup. This setting allows the relay to modify the
51X time inverse overcurrent pickup during shot x. Note that the
rest of 51X settings remain the same. With the modified pickup,
the relay should be able to avoid normal load inrush and well
coordinated with the downstream relays during the autoreclose
or auto zone coordination process.
51R Pickup
Shot x 51R Pickup. This setting allows the relay to modify the
51R residual time inverse overcurrent pickup during shot x. Note
that the rest of 51R settings remain the same. With the modified
pickup, the relay should be able to avoid normal load inrush and
well coordinated with the downstream relays during the
autoreclose or auto zone coordination process.
51Q Pickup
Shot x 51Q Pickup. This setting is reserved for the 51Q negative
sequence time inverse overcurrent.
51P Pickup
Shot x 51P Pickup. This setting allows the relay to modify the
51P phase time inverse overcurrent pickup during shot x. Note
that the rest of 51P settings remain the same. With the modified
pickup, the relay should be able to avoid normal load inrush and
well coordinated with the downstream relays during the
autoreclose or auto zone coordination process.
51P2 Pickup
Shot x 51P2 Pickup. This setting allows the relay to modify the
51P2 phase time inverse overcurrent pickup during shot x. Note
that the rest of 51P2 settings remain the same. With the
modified pickup, the relay should be able to avoid normal load
inrush and well coordinated with the downstream relays during
the autoreclose or auto zone coordination process.
32W Trip
Shot x Block 32W Trip. This setting allows the relay to block or
unblock 32-1 and 32-2 power protections during shot x.
32W Alarm
Shot x Block 32W Alarm. This setting allows the relay to block or
unblock 32-3 power alarm during shot x.
50Q-1 Trip
Shot x Block 50Q-1. This setting is reserved for the 50Q-1
negative sequence instantaneous overcurrent. The same criteria
as 50X-1 Trip.
50Q-2 Trip
Shot x Block 50Q-2. This setting is reserved for the 50Q-2
negative sequence instantaneous overcurrent. The same criteria
as 50X-1 Trip.
50Q-3 Trip
Shot x Block 50Q-3. This setting is reserved for the 50Q-3
negative sequence instantaneous overcurrent. The same criteria
as 50X-1 Trip.
32V Trip
Shot x Block 32V Trip. This setting allows the relay to block or
unblock 32V-1 and 32V-2 Var protections during shot x.
32V Alarm
Shot x Block 32V Alarm. This setting allows the relay to block or
unblock 32V-3 Var alarm during shot x.
Shot x PLC Lockout
Shot x Programmable Lockout. This logic gate has five settings:
Function, IN1, IN2, IN3, and IN4. Program it the same way as
other logic gates. Note that shot 4 does not have the lockout
gate.