IB02602004E
For more information visit: www.eaton.com
Instructional Literature
Effective: May 2008
Page
61
Instructions for the FP-6000 Protective Relay
Table11. System Configuration (continued).
DISPLAY SETTING
DESCRIPTION
SETPOINT RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
Prg w/Bkr:
Program relay with breaker open or closed
(requires 52a or 52b input)
Open or Either
Either
5.4.1
Remote Bkr:
Enable or disable remote breaker open/close
control from rear comm port
Enable or disable
Disable
5.4.1
# Set Grps:
Select the max. number of different Protection
Setting Groups
1, 2, 3 or 4
1
1
5.4.1
9.7
Set Ctrl:
Select the means of control for selecting the
active setting group
Local, Local+
Communications,
Communications, Cin
Local
5.4.1
9.7
Disarm Ctrl:
Enable/disable of the Arm/Disarm control from
the front panel "Test Mode' (Output Trip1 & Trip2
ONLY
Enable or disable
2
Disable
5.4.1
11.2.5.1
Energy Unit:
This is the selection for "Energy Units" killo- or
Mega- watthours
kWh or MWh
kWh
5.4.1
4.6.1.3
TOC Reset T:
Time Overcurrent RESET Time Delay in cycles.
Used when time option for reset is chosen
1 to 20 cycles
4
5
5.4.1
5.4.2.1
8.3.2
Bkr Oper PB:
Front panel Breaker Open/Close pushbutton
function Enable
Enable or disable
Disable
5.4.1
Line Pos Seq
Impedance Ang:
Select the positive sequence line impedance
angle
0 to 90 degrees
70
5.4.1
Line Zero Seq
Impendance Ang:
Select the zero sequence line impedance angle
0 to 90 degrees
70
5.4.1
IR Dir Cntrl:
Select the residual ground polarizing method
Off, dual, 3V0, I
pol
, Neg
Off
5.4.1
Gnd Dir V 3V0 Source:
Select the zero sequence voltage source for
ground direction polarizing
Calculated, Measured
(0=Calculated, 1=Measured)
Calculated
5.4.1
Gnd Dir V 310 Source:
Select the zero sequence voltage source for
ground direction polarizing
Calculated, Measured
(0=Calculated (Ir),
1=Measured(Ix))
Calculated
5.4.1
IX Dir Cntrl:
Select I
x
ground polarizing method
Off, dual, 3V0, I
pol
Off
5.4.1
Ph Dir Switch to Mem:
Select the memory voltage threshold
1 to 15 Volts
(Increments of 1)
3
5.4.1
System Config (L1)
System Configuration Menu
5.4.1
System Control (L2)
System Control Configurations
5.4.1
Temperature Unit
°
C,
°
F
°
C
5.4.1
Motor Config (L2)
Motor Thermal Model Configurations
5.4.1
ThermI Type
Thermal Current Type
RMS, I1 + KI2
RMS
5.4.1
Therm Model
Thermal Model Type
K = User, K = MP
User
5.4.1
I2 Multi K
I2 Percentage K
0.1 to 10.0
6.0
5.4.1
FLA
Full Load Amperes (FLA)
5 to 6000 amps
500 A
5.4.1
LockRotor I
Locked Rotor Current % of FLA (LRC)
300 to1200%
300%
5.4.1
MaxStall Tc
Maximum Allowable Stall Time
1 to 120 seconds
1 s
5.4.1
Service F
Ultimate Trip Current in % FLA (Service Factor)
85 to 150 %
85%
5.4.1
Speed2 FLA
Speed2 Full Load Amperes (FLA2)
5 to 6000 amps
5.4.1
Speed2 LRC
Speed2 Locked Rotor Current % of FLA2 (LRC)
300 to1200%
5.4.1
SP2Stall Tc
Speed2 Maximum Allowable Stall Time
1 to 120 seconds
5.4.1
Speed2 SF
Speed2 Ultimate Trip Current in % FLA2 (Service
Factor)
85 to 150 %
5.4.1