Issue
2
948095
1
V-9955
AUXILLIARY RELAY UNIT
INTRODUCTION
These instructions provide identification,
installation, connection, operation, and
maintenance information for the V-9955
Valcom Auxiliary Relay Unit.
SPECIFICATIONS
Applications
•
Strobe
Activation.
•
Door
Control.
•
Camera
Control.
Features
•
Three 24 VDC 2 Pole Relays with 1 amp
contacts.
•
Screw Terminals for all connections.
•
Independent control or simultaneous
operation of relays.
•
Unit is expandable to 6 relays by adding
V-9957 expansion board.
Dimensions/Weight
•
7.10”H x 4.7”W x 2.10"D
(18.03 cm H x 11.94 cm W x 5.33 cm D)
0.70lbs. (32kg).
Power Requirements
–21.5 to –26 VDC Battery, 20mA per relay
coil.
K1 RELAY
-24
IN *
N/O
N/C STA
-24
IN *
N/O
N/C STA
-24
IN *
N/O
N/C STA
GND
IN *
N/O
N/C STA
GND
IN *
N/O
N/C STA
GND
IN *
N/O
N/C STA
1
15
16
30
K2 RELAY
K3 RELAY
K1 RELAY
K2 RELAY
K3 RELAY
DIODE
ANODE
DIODE
CATHODE
K1
AUX
K3
AUX
K2
AUX
N/C
Terminal Designations
* Denotes Relay Coil