V03-040719
ACTIO 24
Please note that this document is only a short user manual and does not handle every function. The complete manual
is available at
TECHNICAL CHARACTERISTICS
Power circuit
Input voltage
85 … 265 Vac / 120 … 374 Vdc
Frequency
47 … 63 Hz
Maximum consumption
4,6 … 7,5
VA
Environmental conditions
Temperature range
-
10 …. +60ºC
Humidity range
5 …. 95%
Mechanical characteristics
Enclosure material
Plastic UL94
–
V0 Self-extinguishable
Protection grade
IP20
Unit dimensions (Width x Height x Length)
93 x 71 x 58 mm
Weight
180 g
Mounting
DIN Rail (4 modules)
Maximum working altitude
2000 m
Serial interface
Type
RS-485 three wires
Baud rate
9600 / 19200 bps configurable
Data bits
8
Parity
Without parity
Stop bits
1
Characteristics and electrical security
Security
CAT III 300 V under EN 61010
Electric shock protection
Double insulation class II
Digital inputs characteristics
Type
Opto-insulated voltage free (dry contact)
Maximum activation current
50 mA
Analog inputs characteristics
Type
Current
Input range
0 … 20 mA
Resolution in points
1.024 points
Input impedance
100 Ω
Transducer resolution
10 bits
Digital outputs characteristics
Tipo
Relay
Maximum operating power
750 Vac
Maximum operating voltage
250 Vac
Maximum switching current
Resistive load I: 5 Aac
Electrical working life (250 Vac / 5 A)
3 x 10
4
operations
Mechanical working life
2 x 10
7
operations
Standards
Standards
IEC 60664, VDE 0110, UL 94, EN61010-1, EN55011, EN 61000-4-2, EN 61000-
4-3, 61000-4-11, EN 61000-6-4, EN 61000-6-2, EN 61000-6-1, EN 61000-6-3,
EN 61000-4-5, CE