V03-040719
CONNECTIONS AND LEDS
INSTALLATION
ACTIO 24 unit must be installed on an electric panel or enclosure,
attached to a DIN rail (IEC 60715).
The unit must be connected to a power circuit that is protected with
gl (IEC 269) or M type fuses with a rating of 0.5 to 2 A. It must be
fitted with a circuit breaker or equivalent device, in order to be able to
disconnect the unit from the power supply network. The power circuit
must be connected with cables that have a minimum cross-section of
1mm
2
.
The temperature rating of insulation of wires connected to the device
will be at minimum 62ºC.
COMMUNICATION
The device comes equipped with a RS-485 communication port to
read and write the parameters of the device or other devices
connected. The protocol used is Modbus RTU.
By default the device is configured with
peripheral number 97
(decimal) and
baudrate 19200
bps, 8, N, 1
. Using the command for
changing the device number it is possible to assign any other
number (maximum FF in hexadecimal or 255 in decimal).
In case you remember the slave number, you can return to default
number and communication mode following this steps:
•
Power off the device.
•
Press permanently the button.
•
Power on the device and stop pressing the button.
SAFETY PRECAUTIONS
DANGER
Warns of a risk, which could result in personal injury or material damage caused by an incorrect
handling or installation of the unit. In particular, handling with voltages applied may result in electric
shock, which may cause death or serious injury to personnel. Defective installation or maintenance
may also lead to the risk of fire. Read the manual carefully prior to connecting the unit. Follow all
installation and maintenance instructions throughout the unit’s working life. Pay special attention to the
installation standards of the National Electrical Code.
DISCLAIMER
PickData, SL reserves the right to make modifications to the device or the unit specifications set out in this instruction
manual without prior notice.
PickData, SL on its web site, supplies its customers with the latest versions of the device specifications and the most
updated manuals.
MAINTENANCE AND TECHNICAL SERVICE
Device
doesn’t require maintenance.
In the case of any query in relation to unit operation or malfunction, please contact the PickData, SL technical support