background image

 

V03-040719 

 

CONNECTIONS AND LEDS

 

 

INSTALLATION 
 

ACTIO  24  unit  must  be  installed  on  an  electric  panel  or  enclosure, 
attached to a DIN rail (IEC 60715). 
 
The unit must be connected to a power circuit that is  protected  with 
gl  (IEC  269)  or  M  type  fuses  with  a  rating  of  0.5  to  2  A.  It  must  be 
fitted with a circuit breaker or equivalent device, in order to be able to 
disconnect the unit from the power supply network. The power circuit 
must be connected with cables that have a minimum cross-section of 
1mm

2

The temperature rating of insulation of wires connected to the device 
will be at minimum 62ºC. 
 
 

COMMUNICATION 

 

The  device  comes  equipped  with  a  RS-485  communication  port  to 
read  and  write  the  parameters  of  the  device  or  other  devices 
connected. The protocol used is Modbus RTU. 
 
By  default  the  device  is  configured  with 

peripheral  number  97 

(decimal) and 

baudrate 19200

 

bps, 8, N, 1

. Using the command for 

changing  the  device  number  it  is  possible  to  assign  any  other 
number (maximum FF in hexadecimal or 255 in decimal). 
In  case  you  remember  the  slave  number,  you  can  return  to  default 
number and communication mode following this steps: 

 

Power off the device. 

 

Press permanently the button. 

 

Power on the device and stop pressing the button. 

 
SAFETY PRECAUTIONS 
 

 

DANGER 

Warns  of  a  risk,  which  could  result  in  personal  injury  or  material  damage  caused  by  an  incorrect 
handling  or  installation  of  the  unit.  In  particular,  handling  with  voltages  applied  may  result  in  electric 
shock,  which  may  cause  death  or  serious  injury  to  personnel.  Defective  installation  or  maintenance 
may  also  lead  to  the  risk  of  fire.  Read  the  manual  carefully  prior  to  connecting  the  unit.  Follow  all 
installation and maintenance instructions throughout the unit’s working life. Pay special attention to the 
installation standards of the National Electrical Code. 

 

DISCLAIMER 

 

PickData, SL reserves the right to make modifications to the device or the unit specifications set out in this instruction 
manual without prior notice.  
 
PickData, SL on its web site, supplies its customers with the latest versions of the device specifications and the most 
updated manuals. 
 

MAINTENANCE AND TECHNICAL SERVICE 

 

Device 

doesn’t require maintenance. 

In the case of any query in relation to unit operation or malfunction, please contact the PickData, SL technical support 
service. 

 

PickData, SL 

– Technical support service 

Calle Innovació, 3 

08232 

– Viladecavalls (Barcelona), SPAIN 

Tel: (34) 935 117 505 (España) 

 

Email

[email protected]

  

 