ABB Network Partner AB
Apparatus control
Version 1.0-00
1MRK 580 150-XEN
Page 6
-
98
7.3 Setting table
7.3.1 BAYCONx
7.3.2 COMCON
7.3.3 SWICONA
Table 23: Setting table for BAYCONx
PARAMETER:
SETTING RANGE: DESCRIPTION:
T_CAN_RE
0.0-200.0 s
Timeout when the reset of the reservation
acknowledgement is not done by the
requesting bays, for example, because of
communication error. To be set from CAP
531
Table 24: Setting table for COMCON
PARAMETER:
SETTING RANGE: DESCRIPTION:
T_LO_OP
0.0-200.0 s
Maximum time between a select and the
execute command coming from the opera-
tor. Also the maximum time between the
request to override and the following select.
To be set from CAP 531
T_RES
0.0-200.0 s
Allowed time (for BAYCON) to make the
reservation. To be set from CAP 531
Table 25: Setting table for SWICONA
PARAMETER:
SETTING
RANGE:
DESCRIPTION:
T_POSERR
0.0-200.0 s
Allowed time for middle position. To be set
from CAP 531
T_POL
0.0-200.0 s
Time parameter for pole discordance.
Allowed time to have discrepancy between
the poles. To be set from CAP 531
T_SEL
0.0-200.0 s
Allowed time from selection to feedback
select. To be set from CAP 531
T_START
0.0-200.0 s
Allowed time from execute to position indi-
cation change. To be set from CAP 531
T_PULSE
0.0-200.0 s
Time parameter for command output pulse
length. T_PULSE = 0 gives a steady com-
mand output signal. To be set from CAP
531
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......