Disturbance report - Settings
ABB Network Partner AB
1MRK 580 133-XEN
Page
7 - 59
Version 1.0-00
2.1 Recording times
MMI submenu:
Settings
DisturbReport
RecordingTimes
Under this submenu, the different recording times for the Disturbance
Report are set (the pre-fault time, post-fault time, and limit time). These
recording times affect the Disturbance Recorder and Event Recorder func-
tions. The total recording time, tRecording, of a recorded disturbance is:
tRecording = tPre + tPost, or tPre + tLim, depending on which
criterion stops the current disturbance recording.
2.2 Binary signals
MMI submenu:
Configuration
DisturbReport
Input n (1-48)
Up to 48 binary signals can be selected from the signal list, where all
available signals are grouped function by function. The 48 signals can be
selected among internal logical signals and binary input signals. Each
selected signal is registered by the Disturbance Recorder, Event Recorder,
and Indication functions during a recording.
A user-defined name for each of the signals can be entered. This name can
comprise up to 13 characters.
MMI submenu:
Settings
DisturbReport
BinarySignals
For each of the 48 signals, it is also possible to select if the signal is to be
used as a trigger for the start of the Disturbance Report (TrigOperation),
and if the trig should be activated at a logical 1 or 0 level (TrigLevel).
The indications in the Disturbance Summary, that are automatically
scrolled on the MMI when a disturbance is registered, are also selected
from these 48 signals using the Indication Mask.
2.3 Analogue signals
MMI-submenu:
Settings
DisturbReport
AnalogSignals
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......