Another possibility is to set the output from the internal synchro-check
function to a permanently active signal. Set Operation = Release in the
synchro-check function. Then AR01-SYNC is configured to SYNC-
CHECKOK. See Fig. 6.
At confirmation from the synchro-check, or if the reclosing is of single-
phase type, the signal passes on.
At CBReady signal of the Close-Open (CO) type, it is checked that this
signal is present to allow for reclosing.
The synchronism and energizing check is allowed to be fulfilled for a cer-
tain time, tSync. If it does not, or if the other conditions are not fulfilled,
the reclosing is interrupted and blocked.
AR01-INHIBIT
Should this input signal appear, reclosing is inhibited. There is a tInhibit
reset timer, to ensure blocking during a few seconds after the signal is
removed. The input can, for example, be activated by a shunt reactor, or
by delayed back-up protection or breaker-failure protection.
Reclaim timer
This timer defines a period from the issue of a reclosing command, after
which the reclosing function is reset. Should a new tripping occur within
this time, it is treated as a continuation of the first fault.
When the signal to a closing command is given (Pulse AR), the reclaim
timer is started.
There is an AR State Control to track the actual state in the reclosing
sequence.
2.3.9 Pulsing of CB closing
command and
incrementing the
operation counters
• The AR01-CLOSECB, breaker closing command, is made as a pulse
of length, as set by the tPulse 0,1-1 s parameter.
• For breakers without an anti-pumping function, the closing pulse
cutting described below can be used. It is selected by means of the
CutPulse = On parameter. A new tripping pulse, (Trip Int.), then
interrupts the pulse. But the minimum length is always 50 ms.
• At the issue of a reclosing command, the associated reclosing opera-
tion counter is also incremented.
There is a counter for each type of reclosing and one for the total of
all reclosings. See Fig. 7.
2.3.10Transient fault
After the reclosing command, the reclaim timer keeps running for the set
time. If no tripping occurs within this time, tReclaim = 10 to 300 s, the
auto-reclosing function resets after the reclaim time. The breaker remains
closed and the operating gear recharges too, and AR01-CBCLOSED = 1,
AR01-CBREADY = 1.
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......