Apparatus control
ABB Network Partner AB
1MRK 580 150-XEN
Page
6 - 45
Version 1.0-00
Fig. 31
Connections between external synchronising equipment and
the apparatus control modules, alternative 3
In Fig. 28 to Fig. 31, the SY_FAIL input supervises the synchronisation
time. If the relay does not reach synchronism within a certain time,
SY_FAIL is activated and resets the complete operation sequence.
4.2.9 Autoreclosing
Fig. 32 shows the interaction between the autoreclosing (AR) module and
the apparatus control modules. The OR gate for the close signal must have
the same execution cyclicity as the autoreclosing module. The signal
BLK_AR from SWICON is used to block the autoreclose function at the
moment the circuit breaker is under operation.
Fig. 32
Connections between autoreclosing (AR) module and appara-
tus control modules
SWICONB
SY_RUN
SY_FAIL
&
SEL_CLOS
EXE_CLOS
CLOSE
+
-
External synchronising equipment
CB
close
coil
Timer
INPUT
ON
BI/BO
SYNCH
COMCON
CLOSE
EXECUTE
CLOSE
EXECUTE
&
IN
FAULT
≥1
PROGRESS
START
(X80150-31)
SWICONA(B)
&
SEL_CLOS
EXE_CLOS
≥1
AR
INHIBIT
CLOSECB
BLK_AR
CLOSE
Circuit Breaker
To output board
(AR_SEL)
(X80150-32)
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......