ABB Network Partner AB
Pulse counter
Version 1.0-00
1MRK 580 187-XEN
Page 7
-
34
3 Design
The function can be regarded as a function block with a few inputs and
outputs. The inputs are divided into two groups: settings and connectables
(configuration). The outputs are divided into three groups: signals
(binary), service value for SPA, and analogue event for LON.
Fig. 1 shows the Pulse Counter function block with connections of the
inputs and outputs.
Fig. 1
Overview of the Pulse Counter function
The BLOCK and TMIT_VAL inputs can be connected to Single Com-
mand blocks, which are intended to be controlled either from the station
MMI or/and the built-in MMI. As long as the BLOCK signal is set, the
Pulse Counter is blocked. The signal connected to TMIT_VAL performs
one additional reading per positive flank. The signal must be a pulse with
a length
>1
second.
The BIM_CONN input is connected to the used input of the function
block for the Binary input module (BIM). If BIM_CONN is connected to
another function block, the INVALID signal is activated to indicate the
configuration error.
The NAME input is used for a user-defined name with up to 19 charac-
ters.
Each Pulse Counter function block has four output signals: INVALID,
RESTART, BLOCKED, and NEW_VAL. These signals can be connected
to an Event function block for event recording.
PulseCounter
BLOCK
TMIT_VAL
BIM_CONN
NAME
SingleCmdFunc
OUTx
SingleCmdFunc
OUTx
INPUT
Pulse
OUT
I/O-module
BIx
“PCxx-name”
EVENT
INVALID
RESTART
BLOCKED
NEW_VAL
INPUT1
INPUT2
INPUT3
INPUT4
Pulse length
>
1 s
Database
Pulse Counter value:
0...2147483647
LON analogue event data msg
(M_PC_T)
*Identity
*Value
*Time
*Pulse Counter Quality
SMS settings
1. Operation = Off/On
2. Cycle time = 30s...60min
3. Analogue Event Mask = No/Report
(X80187-1)
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......