Fuse-failure supervision function
Version 1.0-00
1MRK 580 169-XEN
Page 5
-
56
4.2 Signal list
4.3 Setting table
IN:
DESCRIPTION:
FUSE-MCB
Functional input sigal, which is normally connected via binary input to the auxiliary NC
contact of the miniature circut breaker in the voltage measuring circuits
FUSE-DISC
Functional input signal, which is normally connected via binary input to the auxiliary NC
contact of the line disconnector
OUT:
DESCRIPTION:
FUSE-VTSU
Output information on the operation of the FFS function. It is supposed to block all voltage
dependent functions within the terminal, except the distance protection. Configure it for
these purposes to the blocking inputs of the relevant functions.
FUSE-VTSZ
Output information on the operation of the FFS function. Its appearence is controlled by
the voltage/current check function. It should block the operation of distance protection
function during fuse-failure conditions in the voltage measuring circuits.
FUSE-VTF3PH
Output signal, which appears five seconds after the fuse-failure condition is detected if the
measured voltages in all three phases are low.
PARAMETER SETTING RANGE
DESCRIPTION
Operation
Off / Zeroseq / Nega-
tiveseq
Operating mode of the fuse-failure supervision function. The opera-
tion can be inhibited or based on measurement of the zero or negative
sequence quantities.
U>
(10-50)% of Ur/sqr(3)
The operating level of the voltage measuring element for the zero
sequence (3.U
0
) or negative sequence (3.U
2
) voltage, set as percent-
age of the terminal rated phase voltage.
I>
(10-50)% of Ir
The operating level of the current measuring element for the zero
sequence (3.I
0
) or negative sequence (3.I
2
) current, set as percentage
of the terminal rated current.
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......