ABB Network Partner AB
Interlocking
Version 1.0-00
1MRK 580 151-XEN
Page 6
-
200
6.2.7 DB_BUS_A
Table 13: Input signals for DB_BUS_A
IN:
DESCRIPTION:
IBxx-Q01_OP
Signal is 1 if Q01 is open
IBxx-Q01_CL
Signal is 1 if Q01 is closed
IBxx-Q1_OP
Signal is 1 if Q1 is open
IBxx-Q1_CL
Signal is 1 if Q1 is closed
IBxx-Q61_OP
Signal is 1 if Q61 is open
IBxx-Q61_CL
Signal is 1 if Q61 is closed
IBxx-Q51_OP
Signal is 1 if Q51 is open
IBxx-Q51_CL
Signal is 1 if Q51 is closed
IBxx-Q52_OP
Signal is 1 if Q52 is open
IBxx-Q52_CL
Signal is 1 if Q52 is closed
IBxx-Q53_OP
Signal is 1 if Q53 is open
IBxx-Q53_CL
Signal is 1 if Q53 is closed
IBxx-Q15_OP
Signal is 1 if Q15 on busbar A is open
IBxx-Q15_CL
Signal is 1 if Q15 on busbar A is closed
IBxx-EXDUP_ES
Signal is 1 if there is no transmission error
from any bay containing earthing switches
Q15
IBxx-EXVVA_ES
Signal is 1 if the interlocking programs in all
bays containing earthing switches Q15 are
running
IBxx-Q61EX1
Input for an external condition for apparatus
Q61
IBxx-Q61EX2
Input for an external condition for apparatus
Q61
IBxx-Q1EX1
Input for an external condition for apparatus
Q1
IBxx-Q1EX2
Input for an external condition for apparatus
Q1
Table 14: Output signals for DB_BUS_A
OUT:
DESCRIPTION:
IBxx-Q01CLREL
Closing of Q01 is allowed
IBxx-Q01CLITL
Closing of Q01 is forbidden
IBxx-Q61REL
Switching of Q61 is allowed
IBxx-Q61ITL
Switching of Q61 is forbidden
IBxx-Q1REL
Switching of Q1 is allowed
IBxx-Q1ITL
Switching of Q1 is forbidden
IBxx-Q51REL
Switching of Q51 is allowed
IBxx-Q51ITL
Switching of Q51 is forbidden
IBxx-Q52REL
Switching of Q52 is allowed
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......