ABB Network Partner AB
Synchronism and energizing
check for single circuit breaker
with voltage selection
Version 1.0-00
1MRK 580 152-XEN
Page 5
-
10
The voltage circuits are arranged differently depending on the number of
synchro-check functions that are included in the control terminal.
In terminals intended for one bay the U-line voltage reference phase is
selected on the man-machine interface (MMI). The reference voltage can
be single-phase L1, L2, L3 or phase-phase L1-L2, L2-L3, L3-L1. The U
-
bus voltage must then be connected to the same phase or phases as are
chosen on the MMI. Fig. 2 shows the voltage connection.
In terminals intended for several bays, all voltage inputs are single phase
circuits. The voltage can be selected for single phase or phase-to-phase
measurement on the MMI. All voltage inputs must be connected to the
same phase or phases.
The circuit breaker can be closed when the conditions for FreqDiff,
PhaseDiff, and UDiff are fulfilled with the UHigh condition.
Fig. 2
Connection of the synchro-check function for one bay
(X80152-2)
U-Line
U-Bus
UL1
UL2
UL3
UN
U
UN
AD
L1,L2,L3
L12,L23
L31
ϕ
U
f
SYN1
AUTOOK
SYN1
MANOK
MMI
Setting
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......