ABB Network Partner AB
Interlocking
Version 1.0-00
1MRK 580 151-XEN
Page 6
-
198
6.2.5 A1A2_DC
Table 9: Input signals for A1A2_DC
IN:
DESCRIPTION:
IIxx-Q11_OP
Signal is 1 if Q11 is open
IIxx-Q11_CL
Signal is 1 if Q11 is closed
IIxx-A1Q15_OP
Signal is 1 if Q15 on busbar A1 is open
IIxx-A1Q15_CL
Signal is 1 if Q15 on busbar A1 is closed
IIxx-A2Q15_OP
Signal is 1 if Q15 on busbar A2 is open
IIxx-A2Q15_CL
Signal is 1 if Q15 on busbar A2 is closed
IIxx-A1DC_OP
Signal is 1 if all disconnectors on busbar A1
are open
IIxx-A2DC_OP
Signal is 1 if all disconnectors on busbar A2
are open
IIxx-VPA1_DC
Switch status of disconnectors on busbar
A1 are valid
IIxx-VPA2_DC
Switch status of disconnectors on busbar
A2 are valid
IIxx-EXDUP_ES
Signal is 1 if there is no transmission error
from any bay containing earthing switches
Q15 in section A1 and A2
IIxx-EXVVA_ES
Signal is 1 if the interlocking programs in all
bays containing earthing switches Q15 in
section A1 and A2 are running
IIxx-EXDUP_BB
Signal is 1 if there is no transmission error
from any bay containing disconnectors con-
nected to the busbar sections A1 and A2
IIxx-EXVVA_BB
Signal is 1 if the interlocking programs in all
bays containing disconnectors connected to
the busbar sections A1 and A2
IIxx-Q11C_EX1
Input for an external close condition for
apparatus Q11
IIxx-Q11C_EX2
Input for an external close condition for
apparatus Q11
IIxx-Q11O_EX1
Input for an external open condition for
apparatus Q11
IIxx-Q11O_EX2
Input for an external open condition for
apparatus Q11
IIxx-Q11O_EX3
Input for an external open condition for
apparatus Q11
Table 10: Output signals for A1A2_DC
OUT:
DESCRIPTION:
IIxx-Q11OPREL
Switching of Q11 is allowed. For GIS open-
ing of Q11 is allowed
IIxx-Q11OPITL
Switching of Q11 is forbidden. For GIS
opening of Q11 is forbidden
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......