ABB Network Partner AB
Interlocking
Version 1.0-00
1MRK 580 151-XEN
Page 6
-
122
If there is no second busbar B and therefore no Q20 and Q2 disconnectors,
then the interlocking for Q20 and Q2 are not used. The states for Q20, Q2,
Q25, BC_AB, BBTR are set to open by setting the appropriate module
inputs as follows. In the functional block diagram, 0 and 1 are designated
0=FIXD-OFF and 1=FIXD-ON:
• Q20_OP = 1
• Q20_CL = 0
• Q2_OP = 1
• Q2_CL = 0
• Q25_OP = 1
• Q25_CL = 0
• BC_AB_CL = 0
• BBTR_OP = 1
4.2.3 Single breaker
arrangement,
transformer bay
4.2.3.1 Signals from bus cou-
pler
If the busbar is divided by bus-section disconnectors into bus sections, the
busbar-busbar connection could exist via the bus-section disconnector and
bus coupler within the other bus section.
Fig. 19
Busbars divided by bus-section disconnectors (circuit break-
ers)
The project-specific logic for input signals concerning bus coupler are the
same as the specific logic for the line bay (ABC_LINE):
BC_AB_CL
Signal if a bus-coupler connection exists between busbar A and B.
VP_BC_AB
The switch status of BC_AB is valid.
Section 1
Section 2
A1
B1
C
A2
B2
C
AB_TRAFO ABC_BC
AB_TRAFO ABC_BC
A1A2_DC(BS)
B1B2_DC(BS)
(X80151-19)
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......