Technical data

Terminal box  GHG 791 01/GHG 721 02

Marking  acc.  to  94/9/EC  and  directice:

II 2 G

Ex e d m ia IIC T6

II 2 D

Ex tD A21 IP 66 T80 °C

EC type examination certificate:

PTB 00 ATEX 3108

Rated  voltage:

up to 690 V

Rated  current:

acc. to table an the inside of the enclosure cover

Perm.  ambient  temperature:

-20° C up to +40° C (catalogue version)

Special versions permit deviating temperature ranges.

Perm. storage temperature in original packing:

-40° C up to +80° C

Schutzart  nach  EN/IEC  60529:

IP 66 (catalogue version)

Insulation class acc. to  EN/IEC 61140:

I -  is complied with by the terminal boxes
II - with internal earth plate

Supply  terminal:

acc. to customers specification and  as certificate

GHG 791 01

max.  4mm²

GHG 791 02

max.  6mm²

Cable  entries:

acc. to customers specification and  as certificate

Test  torques:
Cover  screws

1.20 Nm

Cap nut of the M12 entry

1.65 Nm

Cap nut of the M16 entry

2.50 Nm

Cap nut of the M20 entry

2.50 Nm

Cap nut of the M25 entry

3.50 Nm

Cap nut of the M32 entry

5.00 Nm

Weight  GHG 791 01:
empty weight

approx.  0.25  kg

with internal earth plate

approx.  0.30  kg

Weight  GHG 791 02:
empty weight

approx.  0.45  kg

with internal earth plate

approx.  0.52  kg

Intrinsically  safe  circuits:
Max.  safe  voltage  U

m

690 V

 eff

Safe galvanic isolation from all other circuits
and  earth

Terminal box GHG 791 02

Terminal box GHG 791 01

Terminal box GHG 791 02

Dimensions  in  mm

X  =  fixing  dimensions

www.malux.se