ABB Network Partner AB
Interlocking
Version 1.0-00
1MRK 580 151-XEN
Page 6
-
118
If the busbar is divided by bus-section disconnectors into bus sections, the
signals BBTR are connected in parallel - if both bus-section disconnectors
are closed. So for the basic project-specific logic for BBTR above, add
this logic:
Fig. 15
Busbars divided by bus-section disconnectors (circuit break-
ers)
The following signals from each bus-section disconnector bay
(A1A2_DC) are needed. For B1B2_DC, corresponding signals from bus-
bar B are used. The same type of module (A1A2_DC) is used for different
busbars, that is, for both bus-section disconnector A1A2_DC and
B1B2_DC.
DCOPTR
Signal if the bus-section disconnector is open.
VPDCTR
The switch status of A1A2_DC is valid.
EXDUP_DC
Signal if there is no transmission error from the bay that contains the
above information. This signal is taken from the data valid output on the
command function block.
If the busbar is divided by bus-section circuit breakers, the signals from
the bus-section coupler bay (A1A2_BS), rather than the bus-section dis-
connector bay (A1A2_DC), have to be used. For B1B2_BS, correspond-
ing signals from busbar B are used. The same type of module (A1A2_BS)
is used for different busbars, that is, for both bus-section circuit breakers
A1A2_BS and B1B2_BS.
A1A2OPTR
Signal if there is no bus-section coupler connection between bus sections
A1 and A2.
VPA1A2TR
The switch status of A1A2_DC is valid.
Section 1
Section 2
A1
B1
C
A2
B2
C
ABC_LINE ABC_BC
ABC_LINE
ABC_BC
A1A2_DC(BS)
B1B2_DC(BS)
AB_TRAFO
(X80151-15)
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......