Function:
1 Application
The REC 561 and REL 531 terminals may be provided with output func-
tions that can be controlled either from a Substation Automation System
or from the built-in MMI. The output functions can be used, for example,
to control high-voltage apparatuses in switchyards. For local control func-
tions, the built-in MMI can be used. Together with the configuration logic
circuits, the user can govern pulses or steady output signals for control
purposes within the terminal or via binary outputs. In the REC 561 control
terminal it is also possible to receive data from other contol terminals via
the LON bus.
2 Design
2.1 General
Two types of command function blocks are available, Single Command
and Multiple Command. Eleven Single Command function blocks and 80
Multiple Command function blocks are available in the REC 561 control
terminal. One Single Command function block is available in the REL
531 line terminal.
The output signals can be of the types Off, Steady, or Pulse. The setting is
done on the MODE input, common for the whole block, from the CAP
531 configuration tool (for REC 561) or from SMS (for REL 531).
0=Off sets all outputs to 0, independent of the values sent from the station
level, that is, the operator station or remote-control gateway.
1=Steady sets the outputs to a steady signal 0 or 1, depending on the val-
ues sent from the station level.
2=Pulse gives a pulse with one execution cycle of typical 200 ms dura-
tion, if a value sent from the station level is changed from 0 to 1. That
means that the configured logic connected to the command function
blocks may not have a cycle time longer than 200 ms.
2.2 Single Command
function
The Single Command function block has 16 outputs. The outputs can be
individually controlled from the operator station, remote-control gateway,
or from the built-in MMI. Each output signal can be given a name with a
maximum of 13 characters from the CAP 531 configuration tool (for REC
561) or from SMS (for REL 531).
The output signals, here CDxx-OUT1 to CDxx-OUT16, are then available
for configuration to built-in functions or via the configuration logic cir-
cuits to the binary outputs of the terminal.
The command functions can be connected according to the application
examples in Fig. 1 to Fig. 3. Note that the execution cyclicity of the con-
figured logic connected to the command function block cannot have a
cycle time longer than the command function block.
6
Command function
1MRK 580 165-XEN
Version 1.0-00
November 1996
Optional
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......