Interlocking
ABB Network Partner AB
1MRK 580 151-XEN
Page
6 - 119
Version 1.0-00
EXDUP_BS
Signal if there is no transmission error from the bay that contains the
above information. This signal is taken from the data valid output on the
command function block.
For a bus-coupler bay in section 1, these conditions are valid:
Fig. 16
Signals to a bus-coupler bay in section 1 from any bays in each
section
For a bus-coupler bay in section 2, the same conditions as above are valid
by changing section 1 to section 2 and vice versa.
4.2.2.2 Signals from bus
coupler
If the busbar is divided by bus-section disconnectors into bus sections, the
signals BC_AB from the busbar coupler of the other busbar section must
be transmitted to the own busbar coupler if both disconnectors are closed.
Fig. 17
Busbars divided by bus-section disconnectors (circuit break-
ers)
BBTR_OP (sect.1)
BBTR_OP (sect.2)
BBTR_OP
DCOPTR (A1A2)
&
VP_BBTR (sect.1)
VPDCTR (A1A2)
VP_BBTR
VPDCTR (B1B2)
DCOPTR (B1B2)
VP_BBTR (sect.2)
≥1
&
&
EXDUP_AB (sect.1)
EXDUP_DC (A1A2)
EXDUP_AB
EXDUP_DC (B1B2)
EXDUP_AB (sect.2)
(X80151-16)
Section 1
Section 2
A1
B1
C
A2
B2
C
ABC_BC
ABC_BC
A1A2_DC(BS)
B1B2_DC(BS)
(X80151-17)
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......