Construction and hardware
characteristics - REC 561
ABB Network Partner AB
1MRK 580 148-XEN
Page
2 - 39
Version 1.0-00
3.5 Electrical connections
There are two types of electrical terminals:
• Current-carrying, which is for conductors that have a cross section
of up to 4 mm
2
.
• Voltage connector, which is for conductors up to 2,5 mm
2
, which are
intended for all voltage signals.
The current-carrying terminals are located on position X11. These termi-
nals are feed-through terminal blocks with flat tabs on the internal side.
The voltage connector terminals are divided into two parts:
• A female part for conductor connections.
• A male part mounted inside the case on a circuit board.
All external connectors located on the back side of the case are marked
with designation labels. The female part of the connector is marked with
the same designation label as the male part.
Apply these rules when connecting:
For more information, refer to:
• Installation and commissioning (1MRK 580 166-XEN)
• Buyer’s Guide Series REx 5xx Mechanical design and mounting
accessories (1MRK 514 003-BEN)
If you insert in a socket.....
Then...
One conductor
It can be 0,2-2,5 mm
2
Two conductors
They can be 0,2-1 mm
2
Two 1,5 mm
2
conductors
Use a ferrule
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......