Apparatus control
ABB Network Partner AB
1MRK 580 150-XEN
Page
6 - 89
Version 1.0-00
SAxx-SY_FAIL
To be set to true when the synchro-check
fails and the command execution will stop
SAxx-SY_OK
Closing will be permitted at set to true by the
synchro-check and when SY_RUN is true
SAxx-AR_SEL
Selection input for fast autoreclosing. It is
used only with external selection relays
Table 16: Output signals for SWICONA
OUT:
DESCRIPTION:
SAxx-OX
Indication that the apparatus is in open posi-
tion. Result of the three single phase indica-
tions or blocking of the process updating or
by the manually entered open position
SAxx-CX
Indication that the apparatus is in close
position. Result of the three single phase
indications or blocking of the process updat-
ing or by the manually entered close posi-
tion
SAxx-POS_ERR
Position error. Result of that at least one of
following conditions are fulfilled: One phase
is both open and closed, one phase is in
middle position longer than T_POSERR, the
input POSIND_V is false
SAxx-POL_DISC
Output indicating pole discordance, after
that the time T_POL has elapsed
SAxx-MA_UPD_P
Output indicating manual control of position
updating
SAxx-SEL_OPEN
Selection output for open direction
SAxx-SEL_CLOS
Selection output for close direction
SAxx-EXE_OPEN
Execute output for open direction (settable
pulse length)
SAxx-EXE_CLOS
Execute output for close direction (settable
pulse length)
SAxx-SEL_RES
Reset the selection after successful or failed
operation (pulse output)
SAxx-SEL_ERR
Output indicating a failure in the selection, if
no feedback select signal FDB_SEL is acti-
vated before the time T_SEL has elapsed
SAxx-CMD_ERR
Output indicating a command error. That is
done if the position indication of the exe-
cuted apparatus does not indicate a start in
the position change before the time
T_START has elapsed
Table 15: Input signals for SWICONA
IN:
DESCRIPTION:
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......