ABB Network Partner AB
Synchronism and energizing
check for double circuit breakers
and voltage selection
Version 1.0-00
1MRK 580 167-XEN
Page 5
-
44
1
Set these MMI settings:
2
Apply a single-phase voltage 100% U
r
/sqr3 to the U-bus (U5), and a
single-phase voltage 30% U
r
/sqr3 to the U-line (UL1).
3
Check that the SYN1-AUTOOK and SYN1-MANOK outputs are
activated.
4
Increase the U-Line (UL1) to 60% U
r
/sqr3 and U-Bus(U5) to be equal
to 100% U
r
/sqr3. The outputs should not be activated.
5
The test can be repeated with different values on the U-Bus and the
U-Line.
4.3.2 Dead bus live line
(DBLL)
The test should verify that the energizing function operates for a low volt-
age on the U-bus and for a high one on the U-line. This corresponds to an
energizing of a dead bus from a live line.
1
Change the MMI settings AutoEnerg and ManEnerg to DBLL.
2
Apply a single-phase voltage of 30% U
r
/sqr3 to the U-bus (U5) and a
single-phase voltage of 100% U
r
/sqr3 to the U-line (UL1).
3
Check that the SYN1-AUTOOK and SYN1-MANOK outputs are
activated.
4
Decrease the U-line to 60% U
r
/sqr3 and keep the U-bus equal to 30%
U
r
/sqr3.
The outputs should not be activated.
5
The test can be repeated with different values on the U-bus and the U-
line.
Parameter
Setting
Operation
On
InputPhase
UL1
USelection
SingleBus
AutoEnerg
DLLB
ManEnerg
DLLB
UHigh
80%
U
r
/sqr3
ULow
40%
U
r
/sqr3
FreqDiff
0,05 Hz
PhaseDiff
45°
UDiff
15%
tAutoEnerg
0.5 s
tManEnerg
0.5 s
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......