Apparatus control
ABB Network Partner AB
1MRK 580 150-XEN
Page
6 - 21
Version 1.0-00
EXECUTE command. This must now come together with the OPEN or
CLOSE direction to activate either EXE_OPEN or EXE_CLOS. The con-
nections between SWICON and the output board are shown in Fig. 9.
Fig. 9
Connection of select and execute signals to the command out-
put board from SWICON
Before a selection output is activated, SWICON checks the blocking
(BLK_OPEN/CLOS) and interlocking (INT_LOCK) inputs. After activa-
tion of the selection outputs, the selection timer (T_SEL) starts. When the
feedback select signal does not come in time, SWICON sets the
SEL_ERR output. After the execute outputs are activated, it sets the
CMD_ERR if the position indication does not indicate a start in the posi-
tion change, before the time T_START has elapsed.
Automatic operation is included in SWICON. It has an input for bay
information concerning permission for automatic operation (AU_OP_V).
It also has an output that indicates permission per apparatus (AU_OP_P).
For synchro-check, SWICON has two versions. One version (SWICONA)
is for a synchro-check relay that checks the synchronisation condition
continuously and gives a signal on SY_OK if there is synchronism, see
Fig. 28. This is the normal application when the internal synchro-check
function is used. To close the breaker, SWICON can activate the
EXE_CLOS output at the activation of the SY_OK signal, when the
CLOSE and EXECUTE inputs are already set and also when the
SEL_CLOS output is set. The SY_RUN input is set to FIXD-ON. If not,
the SY_OK input is used; it also sets to FIXD-ON.
SWICON
&
&
≥1
SEL_OPEN
SEL_CLOS
EXE_OPEN
EXE_CLOS
FDB_SEL
Apparatus 1
SELECTED
OPEN
CLOSE
To MMI
OPEN
CLOSE
EXECUTE
CANCEL
To output board
From
COMCON
SELECT
From BAYCON
(X80150-9)
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......